Field Wiring Applications With Conventional Thermostat - Haier GE NF97UM Service Manual

97% upflow/horizontal modulating variable speed gas furnace
Hide thumbs Also See for GE NF97UM:
Table of Contents

Advertisement

Field Wiring Applications with Conventional Thermostat

Thermostat
DIP Switch 1
1 Heat / 1 Cool
NOTE:
Use DIP
switch 3 to set
ON
sceond-stage heat
ON delay.
OFF - 7 minutes
ON - 12 minutes
1 Heat / 2 Cool
NOTE:
Use DIP
switch 3 to set
ON
sceond-stage heat
ON delay.
OFF - 7 minutes
ON - 12 minutes
1 Heat / 2 Cool
with t'stat with
dehumidification
mode
NOTE:
Use DIP
ON
switch 3 to set
sceond-stage heat
ON delay.
OFF - 7 minutes
ON - 12 minutes
* "R" required on some units.
** Connect W1 to W1 ONLY if using defrost tempering kit
DIP Switch Settings and On-Board Links
W915
(Y1 to Y2)
(DS to R)
Two-Stage Cooling
Dehumidification
Intact
Cut
Cut
Table 31. Field Wiring
Page 66
W914
W951
(O to R)
Heat Pumps
Intact
Intact
Intact
Intact
Cut
Intact
Wiring Connections
CONTROL
OUTDOOR
T'STAT
TERM. STRIP
CONTROL
OUTDOOR
T'STAT
TERM. STRIP
UNIT
CONTROL
OUTDOOR
T'STAT
TERM. STRIP
31-5000723 Rev. 0
UNIT
*
*
UNIT
*