Haier GE NF97UM Installation Instructions Manual
Haier GE NF97UM Installation Instructions Manual

Haier GE NF97UM Installation Instructions Manual

Warm air gas furnace upflow/horizontal left/right air discharge direct vent
Hide thumbs Also See for GE NF97UM:

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
NF97UM
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to
the potential for personal injury or death.
NOTICE
A thermostat is not included and must be ordered
separately.
In all cases, setup is critical to ensure proper system
operation.
Field wiring is illustrated in these instructions.
GE Appliances
A Haier Company
Appliance Park
Louisville, KY 40225
507028-05G / 31-5000694
This manual must be left with the homeowner for future reference.
Warm Air Gas Furnace
Upflow/Horizontal Left/Right
Air Discharge Direct Vent

Table of Contents

Gas Furnace ................................................................4
Shipping and Packing List ...........................................4
Safety Information .......................................................4
General ........................................................................6
Installation ...................................................................6
Filters .........................................................................10
Duct System ..............................................................10
Venting Practices .......................................................12
Gas Piping .................................................................26
Electrical ....................................................................29
Blower Performance ..................................................39
Gas Valve Operation .................................................44
Unit Start-Up ..............................................................44
Other Unit Adjustments..............................................48
Heating Sequence of Operation ................................49
Service.......................................................................50
Integrated Control Diagnostic Codes.........................52
Repair Parts List ........................................................57
*P507028-05G*
Issue 2128
(P) 507028-05G
Page 1 of 66

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GE NF97UM and is the answer not in the manual?

Questions and answers

Summary of Contents for Haier GE NF97UM

  • Page 1: Table Of Contents

    Repair Parts List ............57 In all cases, setup is critical to ensure proper system operation. Field wiring is illustrated in these instructions. GE Appliances *P507028-05G* A Haier Company Appliance Park (P) 507028-05G Louisville, KY 40225 507028-05G / 31-5000694 Issue 2128...
  • Page 2 Unit Dimensions EXHAUST AIR 3-1/4 OUTLET (83) 1-7/8 (48) Flue Condensate Trap Assembly Furnished for external SUPPLY AIR OPENING field installation (178) on either side of unit. (See installation instructions COMBUSTION for additional AIR INTAKE information.) OPTIONAL 23-3/4 SIDE RETURN (603) AIR FILTER KIT (Either Side)
  • Page 3 Parts Arrangement BURNER BOX ASSEMBLY PRESSURE SWITCHES HEAT EXCHANGER VARIABLE CAPACITY PRIMARY LIMIT GAS VALVE VARIABLE SPEED COMBUSTION AIR INDUCER BAG ASSEMBLIES (shipping location) COLD END HEADER ACCESS PANEL VARIABLE SPEED BLOWER MOTOR SHIPPING BLOCK (-135 UNITS ONLY) CONTROL BOX (includes variable capacity integrated control transformer, circuit breaker and door switch) Figure 1.
  • Page 4: Warning

    Gas Furnace Safety Information The NF97UM Category IV gas furnace is equipped with a variable capacity, variable speed integrated control. Each DANGER NF97UM is shipped ready for installation in the upflow, DANGER OF EXPLOSION! horizontal left air discharge or horizontal right air discharge position.
  • Page 5 For installation in a residential garage, the furnace must be In Canada, all electrical wiring and grounding for the unit installed so that the burner(s) and the ignition source are must be installed according to the current regulations of located no less than 18 inches (457 mm) above the floor. the Canadian Electrical Code Part I (CSA Standard C22.1) The furnace must be located or protected to avoid physical and/or local codes.
  • Page 6: General

    All furnace operating conditions (including ignition, NOTE: The Commonwealth of Massachusetts stipulates input rate, temperature rise and venting) must these additional requirements: be verified in accordance with these installation • Gas furnaces shall be installed by a licensed plumber instructions. or fitter only.
  • Page 7 SETTING EQUIPMENT UPFLOW APPLICATION Place level on blower Place level on deck screws to check the front blower forward tilt deck to check side to side UNIT FRONT AIR FLOW 1/2” max. SIDE VIEW HORIZONTAL APPLICATION UNIT FRONT AIR FLOW 1/2”...
  • Page 8 removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing. 20” X 25” X 1” (508mm X 635mm X 25mm) Air Filter Return Plenum Transition Figure 6.
  • Page 9 Horizontal Applications Suspended Installation of Horizontal Unit This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or WARNING floor joists, as shown in Figure 12 or install the furnace on a platform, as shown in Figure 13.
  • Page 10: Filters

    Supply Air Plenum If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection (by reflected light) of the heat exchanger for leaks after the furnace is installed.
  • Page 11 Use PVC primer and solvent cement or ABS solvent Piping and Fittings Specifications cement meeting ASTM specifications, refer to Table 2. As an alternate, use all purpose cement, to bond ABS, Schedule 40 PVC (Pipe) D1785 PVC, or CPVC pipe when using fittings and pipe made of Schedule 40 PVC (Cellular Core Pipe) F891 the same materials.
  • Page 12: Venting Practices

    during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular CAUTION core pipe. Do not discharge exhaust into an existing stack or NOTE: Assembly should be completed within 20 stack that also serves another gas appliance. If vertical seconds after last application of cement.
  • Page 13 STANDARD CONCENTRIC Outdoor Outdoor Exhaust Exhaust Flush Mount 1-1/2" 2" Concentric 3" Concentric VENT Accelerator Accelerator Concentric Kit Capacity PIPE DIA. (Dia. X Length) (Dia. X Length) (in.) 71M80 69M29 60L46 1-1/2" x12" 2" x12" 51W11** +44W92++ +44W92++ 44W93+ 1-1/2 2-1/2"...
  • Page 14 Use the steps in Figure 16 to correctly size vent pipe NFPA 54 in U.S.A., and current CSA-B149 Natural Gas diameter. and Propane Installation Codes in Canada for details. Position termination according to location given in Figure 20. In addition, position termination so it is free from any obstructions and 12”...
  • Page 15 TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW 2” EXHAUST EXHAUST INTAKE INTAKE 2” 2” 2” 2” 2” 3” 3” 070 Only 1−1/2” TRANSITION Exhaust 2” 6” Min Exhaust DO NOT transition from larger to smaller DO NOT transition pipe in horizontal runs from smaller to larger Exhaust of exhaust pipe.
  • Page 16 Maximum Allowable Exhaust Vent Pipe Length (in ft.) without Insulation in Unconditioned Space For Winter Design Temperatures Single - Stage High Efficiency Furnace Unit Input Size Winter Design Temperatures Vent Pipe ºF (ºC) Diameter 1-1/2 in. 32 to 21 2 in. (0 to -6) 2-1/2 in.
  • Page 17 Maximum Allowable Intake or Exhaust Vent Length (feet) Standard Termination at Elevation 0 - 4,500 ft 1-1/2” Pipe 2” Pipe 2-1/2” Pipe 3” Pipe Number of Model Model Model Model 90° Elbows Used Standard Termination at Elevation 4,501 - 10,000 ft 1-1/2”...
  • Page 18 Maximum Allowable Intake or Exhaust Vent Length (feet) Concentric Termination at Elevation 0 - 4,500 ft 1-1/2” Pipe 2” Pipe 2-1/2” Pipe 3” Pipe Number of Model Model Model Model 90° Elbows Used Concentric Termination at Elevation 4,501 - 10,000 ft 1-1/2”...
  • Page 19 VENT TERMINATION CLEARANCES FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA INSIDE CORNER DETAIL Fixed Operable Fixed Closed Closed Operable AREA WHERE TERMINAL AIR SUPPLY INLET VENT TERMINAL IS NOT PERMITTED US Installations Canadian Installations Clearance above grade, veranda, 12 inches (305mm) or 12 in.
  • Page 20 FIELD FABRICATED WALL TERMINATION NOTE − FIELD−PROVIDED REDUCER MAY BE 2” (51mm) 3” (76mm) REQUIRED TO ADAPT LARGER VENT PIPE SIZE Vent Pipe Vent Pipe TO TERMINATION A− Minimum clearance above grade or average 12” (305 mm) 12” (305 mm) snow accumulation B−...
  • Page 21 Details of Intake and Exhaust Piping Terminations for Direct Vent Installations NOTE: In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors. NOTE: Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building Inlet Air material, a corrosion resistant shield (minimum 24 inches...
  • Page 22 If intake and exhaust piping must be run up a side FIELD-PROVIDED 1-1/2” (38mm) accelerator wall to position above snow accumulation or other REDUCER MAY BE REQUIRED provided on 71M80 & 44W92 TO ADAPT DIFFERENT VENT kits for -045 and -070 models obstructions, piping must be supported every 24”...
  • Page 23 Condensate Piping line were to become restricted. This unit is designed for either right or left side exit of Horizontal furnace (Figure 33 or Figure 36) - In condensate piping in upflow applications. In horizontal horizontal furnace applications, the field provided vent applications, the condensate trap must extend below the must be a minimum 4”...
  • Page 24 Optional Condensate Drain Connection Adapter 3/4 inch slip X 3/4 inch mpt (not furnished) 90° Elbow 3/4 inch PVC (not furnished) Adapter 3/4 inch slip X 3/4 inch mpt (not furnished) Condensate Drain Connection In Unit 1 (25 mm) Min. Vent 2 (50 mm) Max.
  • Page 25 (Unit shown in horizontal left-hand discharge position) Field Provided Vent Evaporator (4” min. to 5” max. above Coil condensate drain connection) 4”min 5”max 5’ max. PVC Pipe Only Condensate Drain Connection (Trap at coil is optional) Drain Pan Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap Figure 33.
  • Page 26: Gas Piping

    When connecting gas supply, factors such as length of run, number of fittings and furnace rating must be IMPORTANT considered to avoid excessive pressure drop. Table 8 lists recommended pipe sizes for typical applications. When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must NOTE: Use two wrenches when connecting gas piping be vented to relieve pressure in order for the furnace...
  • Page 27 Gas Pipe Capacity - FT³/HR (kL/HR) Nominal Length or Pipe - feet (m) Internal Iron Pipe Diameter Size - - inches inches (3.048) (6.096) (9.144) (12.192) (15.240) (18.288) (21.336) (24.384) (27.432) (30.480) (mm) (mm) .622 (12.7) (17.799) (4.96) (3.40) (2.75) (2.32) (2.07) (1.87)
  • Page 28 IMPORTANT WARNING When testing pressure of gas lines, gas valve must be FIRE OR EXPLOSION HAZARD disconnected and isolated. See Figure 38. Gas valves Failure to follow the safety warnings exactly could can be damaged if subjected to pressures greater than result in serious injury, death, or property damage.
  • Page 29: Electrical

    Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in WARNING the current standards of the National Fuel Gas Code ANSI Z223.1. CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each Electrical appliance connected to the venting system being placed into operation could result in carbon monoxide...
  • Page 30 The unit is equipped with a field makeup box. The makeup terminals. See Figure 44 for location of terminal. This box may be moved to the right side of the furnace to terminal is energized in the heating mode when the facilitate installation.
  • Page 31 Generator Use - Voltage Requirements Switch 3 - Second Stage Heat On Delay - If a single stage thermostat is used, the integrated control can be The following requirements must be kept in mind when used to energize second stage heat after either 7 minutes specifying a generator for use with this equipment: or 12 minutes of first stage heat operation.
  • Page 32 • Once demand is met, motor runs at 50% for 30 Speed Switch 8 Switch 9 seconds then ramps down to stop. 1 - Low 2 - Medium Low 3 - Medium High 4 - High (factory) Table 13. Cooling Mode Blower Speeds Ramping Option “B”...
  • Page 33 Error Code Recall Mode - Select “E” from the menu to Blower DIP Switch Settings Thermostat access the most recent 10 error codes. Select “c” from the Speed Demand Error Code Recall menu to clear all error codes. Button Adjustments must be pressed a second time while “c”...
  • Page 34 Figure 43. Typical Field Wiring Diagram Page 34 of 66 Issue 2128 507028-05G / 31-5000694...
  • Page 35 NEUTRAL COMBUSTION TERMINALS AIR INDUCER CONNECTOR IGNITOR FLAME CONNECTOR SENSE DIAGNOSTIC LINE VOLTAGE PUSH BUTTON TERMINALS DIP SWITCHES INDOOR BLOWER CONNECTOR OUTDOOR AIR SENSOR TERMINALS 7-SEGMENT DIAGNOSTIC LED W915 Y1 TO Y2 DISCHARGE AIR SENSOR W951 R TO O TERMINALS W914 R TO DS FACTORY TEST W915...
  • Page 36 DIP Switch Settings and On-Board Links W915 W914 W951 Thermostat Wiring Connections (Y1 to Y2) DIP Switch 1 (DS to R) (Oto R) Two-Stage Dehumidification Heat Pumps Cooling FURNACE OUTDOOR T'STAT TERM. STRIP UNIT 1 Heat / 1 Cool NOTE: Use DIP switch 3 to set Intact...
  • Page 37 DIP Switch Settings and On-Board Links W915 W914 W951 Thermostat Wiring Connections (Y1 to Y2) DIP Switch 1 (DS to R) (Oto R) Two-Stage Dehumidification Heat Pumps Cooling FURNACE OUTDOOR T'STAT TERM. STRIP UNIT 2 Heat / 2 Cool Intact Intact *Not required on all units FURNACE...
  • Page 38 DIP Switch Settings and On-Board Links W915 W914 W951 Thermostat Wiring Connections (Y1 to Y2) DIP Switch 1 (DS to R) (Oto R) Two-Stage Dehumidification Heat Pumps Cooling FURNACE HEAT PUMP TERM. STRIP T'STAT 67M41* Dual Fuel Single- Stage Heat Pump Thermostat w/dual Intact Intact...
  • Page 39: Blower Performance

    Blower Performance NF97U070M3B BLOWER PERFORMANCE (less filter) HEATING BLOWER PERFORMANCE Heating Input Range and Blower Volume - CFM Heating Adjust CFM Selections 100% Increase (+15%) Heat CFM 1030 1128 Increase (+7.5%) Heat CFM 1048 Default Heat CFM Decrease (-7.5% ) Heat CFM Decrease (-15% ) Heat CFM COOLING BLOWER PERFORMANCE Blower Speed Selections...
  • Page 40 NF97U090M4C BLOWER PERFORMANCE (less filter) HEATING BLOWER PERFORMANCE Heating Input Range and Blower Volume - CFM Heating Adjust CFM Selections 100% Increase (+15%) Heat CFM 1101 1234 1367 1500 1633 Increase (+7.5%) Heat CFM 1028 1155 1281 1407 1534 Default Heat CFM 1075 1195 1314...
  • Page 41 NF97U110M5C BLOWER PERFORMANCE (less filter) HEATING BLOWER PERFORMANCE Heating Input Range and Blower Volume - CFM Heating Adjust CFM Selections 100% Increase (+15%) Heat CFM 1049 1237 1424 1612 1800 1988 Increase (+7.5%) Heat CFM 1000 1174 1349 1524 1699 1874 Default Heat CFM 1112...
  • Page 42 Model -15% -7.5% Default +7.5% +15% All Models Allowed Allowed Factory Setting Allowed Allowed Table 19. Allowable Heating Speeds Model 38% of Second Stage Cooling All Models Allowed Table 20. Allowable Circulation Speeds Operating Sequence System Demand System Response Thermostat Relative Humidity Blower Demand...
  • Page 43 Operating Sequence System Demand System Response Thermostat Demand Relative Humidity Blower System Step Compressor Comments Condition (COOL) Status Stage Stage NO CALL FOR DEHUMIDIFICATION Normal Operation Acceptable Compressor and indoor - Y1 blower follow thermostat Normal Operation demand Acceptable High 100% - Y2 ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING...
  • Page 44: Gas Valve Operation

    Wait for the combustion air inducer to stop. Set the Unit Start-Up thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes. FOR YOUR SAFETY READ BEFORE OPERATING Adjust the thermostat to deactivate the heating demand and again wait for the combustion air inducer to stop.
  • Page 45 Gas Pressure Measurement NEGATIVE AIR POSITIVE AIR PRESSURE PORT PRESSURE PORT Gas Flow (Approximate) Seconds for One Revolution Natural Capacity 1 cu ft 2 cu ft 1 cu ft 2 cu ft OUTLET Dial Dial Dial Dial INLET -070 -090 -110 SUPPLY MANIFOLD...
  • Page 46 After allowing unit to stabilize for 5 minutes, record High Altitude Information manifold pressure and compare to value given in NOTE: In Canada, certification for installation at elevations Table 26. over 4500 feet (1372 m) is the jurisdiction of local Repeat steps 3, 4 and 5 on HIGH HEAT.
  • Page 47 Gas Valve Field Installed Figure 46. Manifold Pressure Measurement Negative Port Positive Port Red and Black Tubing - Black Tubing + Gas Valve Field Installed Measuring Device Figure 47. Operation Signal (Delta P) Measurement 507028-05G / 31-5000694 Issue 2128 Page 47 of 66...
  • Page 48: Other Unit Adjustments

    Exhaust and Air Intake Pipe Other Unit Adjustments Check exhaust and air intake connections for tightness and to make sure there is not blockage. Primary Limit Are pressure switches closed? Obstructed exhaust The primary limit is located on the heating compartment pipe will cause unit to shut off at pressure switches.
  • Page 49: Heating Sequence Of Operation

    When the demand for high fire (second stage) heat Heating Sequence of Operation is satisfied, the gas valve is de-energized and the field selected indoor blower off delay begins. The The integrated control initiates a pressure switch combustion air inducer begins a 20 second post purge calibration at the initial unit start-up on a call for heat.
  • Page 50: Service

    When the demand for first and second stage heat Service is satisfied, the gas valve is de-energized and the field selected indoor blower OFF delay begins. The combustion air inducer begins a 20 second post-purge period. WARNING When the combustion air post-purge period is ELECTRICAL SHOCK, FIRE, OR EXPLOSION complete, the inducer is de-energized.
  • Page 51 Winterizing and Condensate Trap Care 17. Remove two screws from the front cabinet flange at the blower deck. Spread cabinet sides slightly to allow Turn off power to the unit. clearance for removal of heat exchanger. Have a shallow pan ready to empty condensate water. 18.
  • Page 52: Integrated Control Diagnostic Codes

    Planned Service 38. Reinstall burner box cover. A service technician should check the following items 39. Reconnect 2 pin plug to gas valve. during an annual inspection. Power to the unit must be 40. Replace the blower compartment access panel. shut off for the service technician’s safety.
  • Page 53 Code Diagnostic Codes / Status of Equipment Action Required to Clear and Recover Idle mode (Decimal blinks at 1 Hertz - 0.5 seconds ON, 0.5 seconds OFF). Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5 seconds OFF) / cfm setting for current mode displayed.
  • Page 54 Code Diagnostic Codes / Status of Equipment Action Required to Clear and Recover E202 Indoor blower motor mismatch - indoor motor Incorrect appliance capacity code selected. Check for horsepower does not match unit capacity proper configuring under Unit Size Code for Furnace/ Air Handler on configuration guide or in installation instructions.
  • Page 55 Code Diagnostic Codes / Status of Equipment Action Required to Clear and Recover E240 Low flame current - Run mode- Refer to Check micro-amperes of flame sensor using control troubleshooting diagnostics or field installed mode. Clean or replace sensor. Measure voltage of neutral to ground to ensure good unit ground.
  • Page 56 Code Diagnostic Codes / Status of Equipment Action Required to Clear and Recover E292 Indoor blower motor unable to start due to Indoor blower motor unable to start (seized bearing, obstructed wheel seized bearings. stuck wheel, etc.) Replace motor or wheel if assembly does not operate or meet performance standards.
  • Page 57: Repair Parts List

    Repair Parts List The following repair parts are available through GEA distributors. When ordering parts, include the complete furnace model number listed on the nameplate. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier. Cabinet Parts Heating Parts •...
  • Page 58 Program Unit Capacity / Size Mode Power-Up - Number displayed by integrated control represents unit size code (furnace model and capacity). If three horizontal bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following: Turn room thermostat to OFF.
  • Page 59 Troubleshooting: Heating Sequence of Operation IGNITION AND CALL FOR LOW FIRE WITH TWO-STAGE THERMOSTAT Safety Check Verify There Is No Main Burner Flame After Indoor blower OFF Heat OFF Delay (Low Heat Speed) Limit Combustion Air Limit Indoor Blower De-Energize Error Code Inducer On Switch...
  • Page 60 Troubleshooting: Heating Sequence of Operation (continued) CALL FOR HIGH FIRE WITH TWO-STAGE THERMOSTAT 2 Stage Thermostat 1st Call for High Fire? 2nd Stage Recognition Delay (30 Seconds) Combustion Air Inducer ON (100% Rate Speed) High Pressure Switch Increase Combustion Error Code Wait 5 Closes Within Air Inducer Speed...
  • Page 61 Troubleshooting: Heating Sequence of Operation (continued) RUN MODE (TWO-STAGE THERMOSTAT) RUN MODE (SINGLE-STAGE THERMOSTAT) FIRST OR SECOND-STAGE CALL FOR HEAT ALL INPUTS MONITORED (LIMIT, PRESSURE, ALL INPUTS MONITORED (LIMIT, PRESSURE, CALL FOR HEAT/COOL, FLAME LEVEL). CALL FOR HEAT/COOL, FLAME LEVEL). 2nd Stage Heat 2nd Stage Call for Heat...
  • Page 62 Troubleshooting: Heating Sequence of Operation (continued) IGNITION AND CALL FOR HEAT WITH SINGLE-STAGE THERMOSTAT Safety Check Verify There Is No Main Burner Indoor Blower OFF After Flame Heat OFF Delay (Low Heat Speed) Indoor Blower Limit Limit De-Energize Combustion Air Error Code Switch Closes Within 3...
  • Page 63 Troubleshooting: Cooling Sequence of Operation CALL FOR COOLING 1st Stage Cooling Request Received Energize 1st Stage Cooling Contactor (Compressor & Fan) Indoor Blower On After 2-second delay Energize Indoor Blower (Per Ramping Profile) 1st Stage 2nd Stage Cooling Request Cooling Still Active? Request? Energize 2nd Stage...
  • Page 64 Troubleshooting: Continuous Fan Sequence of Operation CONTINUOUS LOW SPEED INDOOR BLOWER SEQUENCE OF OPERATION Call for Continuous Blower Indoor Blower On (Speed Determined by Dip Switch settings) Request Maintain Indoor for Cooling Go to Call for Cooling Blower at set speed Received? Go to Call for Heat -- Two-Stage Thermostat Request...
  • Page 65 Requirements for Commonwealth of Massachusetts Modifications to NFPA-54, Chapter 10 INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas-fueled equipment Revise NFPA-54 section 10.8.3 to add the following shall not approve the installation unless, upon requirements: inspection, the inspector observes carbon monoxide For all side wall, horizontally vented, gas-fueled equipment...
  • Page 66 For the Province of Ontario, Horizontal Sidewall Vent Applications Only For exterior horizontal venting applications, the 2” X 1.5” reducer for 2” venting at the point where the exhaust pipe exits the structure is not required in direct or nondirect vent applications in the Province of Ontario. In these applications, the vent should be oriented such that the exhaust plume is unobjectionable.