Wiring And Sequence Of Operation - Haier GE NF96UV Service Manual

96% upflow/horizontal two stage variable speed gas furnace
Hide thumbs Also See for GE NF96UV:
Table of Contents

Advertisement

Wiring and Sequence of Operation

LINE VOLTAGE - FACTORY
LINE VOLTAGE - FIELD
LOW VOLTAGE - FACTORY
LOW VOLTAGE - FIELD
NOTES:
1.
PRESS AND RELEASE FAULT CODE HISTORY BUTTON TO
DISPLAY FAULT CODES. TO ERASE CODES, PRESS AND
HOLD BUTTON IN FOR MORE THAN 5 SECONDS
1.
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING
MATERIAL HAVING A TEMP. RATING OF AT LEAST 90°c.
2.
PROPER POLARITY MUST BE OBSERVED FOR FIELD LINE VOLTAGE SUPPLY; IGNITION CONTROL WILL LOCK OUT IF POLARITY
IS REVERSED.
3.
FOR TEMPORARY SERVICE REPLACEMENT OF CIRCULATING BLOWER MOTOR WITH PSC MOTOR, CONNECT DESIRED SPEED
TAP TO "EAC" TERMINAL AND NEUTRAL TAP TO NEUTRAL TERMINAL ON IGNITION CONTROL.
4.
DO NOT CONNECT C (COMMON) CONNECTION BETWEEN INDOOR UNIT AND THERMOSTAT EXCEPT WHEN REQUIRED BY THE
INDOOR THERMOSTAT. REFER TO THE THERMOSTAT INSTALLATION INSTRUCTIONS.
Figure 53. Typical Wiring Diagram
Page 52
31-5000726 Rev. 0