Hisense AKT26UR4RK4 Use And Installation Instructions page 27

Table of Contents

Advertisement

Available languages

Available languages

3.5 Concealed Installation
Only items peculiar to this installation method are given here. See 3.3Exposed Installation for additional
instructions.
Install the unit according to the instructions below. Failure to do so may cause lead to both cooling
and heating failure and the condensation inside the house.
(1) Allow enough space between the main unit and ceiling not to obstruct the flow of cool/warm air.
(2) Place a partition plate between outlet and inlet sections.
(3) Plate a partition plate on the right side.
(4) Change the upward-blow limit switch.
(5) Use a movable lattice at the air outlet to allow the adjustment of cool/warm air flow direction.
(6) Lattice size should be 70% or more of open rate.
50 or more
3.5.1 Wall hole
·See 3.3.1 Refrigerant piping under 3.3 Exposed Unit Installation.
3.5.2 Changing upward air flow dipswitch
·Change the upward air flow dipswitch to ON to limit the upward air flow.
(1) Remove the front grille.
(2) Switch the dipswitch on the PCB in the electrical equipment box to ON.
CAUTION
Be sure to turn on the upward air flow switch. Failure to do so may cause incomplete cooling/heating and
formation of condensation inside the house.
50 or more
Partition plate
Installation and Maintenance
Right side partition plate
Upper lattice
must not
project
Movable lattice
Partition plate
70% or more
of open rate
Partition plate
Movable lattice
24
(Unit: mm)
Right side partition plate
20~30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Akt35ur4rk4Akt52ur4rk4

Table of Contents