cables to the TrakMax until the TrakMax has been connected to the positive and negative terminals of the
battery bank.
It is recommended to use a strain relief (bushings, connectors, clamp connectors, or wire glands) in each of the
three ¾ in openings.
The NEC requires that the wires carrying the system current never exceed 80% of the conductor's current
rating. The table below provides the minimum size of copper wire allowed by NEC. Wire types rated for 75°C
and 90°C are included.
1) Remove the Wiring End Cover from the Top Cover by removing the four securing screws as shown below.
2) Route the relevant cable/wire through the appropriate ¾ in opening as noted on the cover.
Note: If strain reliefs (i.e.: cable clamps, wire glands) are being used, they must be installed prior to routing
the wire, and the wire should route through the clamp.
3) Terminal connectors for DC wiring are located on the lower edge of the circuit board. Once the
wires have been installed, tighten the terminals with the screw located on the top of the terminals to 1.2Nm
(10.6lb-in). Be careful not to over tighten.
Page 9 of 29
Wire Type
Copper
6 AWG (16 mm
Aluminum
4 AWG (25 mm
windynation
75°C Wire
90°C Wire
2
)
8 AWG (10 mm
2
)
6 AWG (16 mm
2
)
2
)
05/06/2015