The TrakMax uses voltage set points to determine when to disconnect or reconnect loads depending on battery
voltage. TrakMax prevents damage to the battery from over-discharge during periods of poor weather or
excessive loads and can charge the batteries in this function.
4.9.1

Low Voltage Disconnect

The TrakMax will disconnect the load from the batteries when it reaches the low voltage disconnect (LVD)
setting as shown in the table below.
Battery Voltage
12V
24V
48V
4.9.2

Low Voltage Reconnect

The TrakMax will also provide automatic reconnection of the loads at the low voltage reconnect (LVR) setting.
Reconnection of the load is allowed once the battery voltage has exceeded the low voltage reconnect (LVR)
setting as shown in the table below.
Battery Voltage
12V
24V
48V

5 ERROR CONDITIONS

When the ERROR Symbol
system and an error code will appear in the second line on the display.
The list of Error codes is presented in the table below and can help identify a possible equipment failure, fault or
incorrect setting - configuration. All attempts to correct or clear a fault must be performed by qualified personnel.
Typically, the error can be cleared once the fault is removed but a restart of the charge controller is
recommended after each attempt to remedy the situation by removing battery power for 30 seconds.
If after restarting the controller the error remains, it may indicate a fatal error and will require you to contact the
supplier or Windy Nation for warranty services.
Error Code Description
101
EEPROM Fault
102
Remote Communication Fault
103
Low Input PV Voltage
104
High Input PV Voltage
105
Low Battery Voltage (<9.0V)
Page 23 of 29
Maintenance Free
Lead Acid
10.5V
21.0V
42.0V
Maintenance Free
Lead Acid
12.0V
24.0V
48.0V
appears in the LCD display the controller has detected an abnormality in the
Possible Remedies
• Power down and restart the controller.
• Check Remote Monitor connections.
• Verify cable is correctly wired
• Check cable for any damage
• Ensure the PV panel is in direct sun-light.
• Remove PV connection and check the PV voltage.
• Remove PV connection and check the PV voltage.
• Adjust solar panel wiring to be within acceptable range
• Check the battery voltage.
• Charge battery as necessary
Battery Type
Deep Cycle
Gel
Wet Lead Acid
10.5V
21.0V
42.0V
Battery Type
Deep Cycle
Gel
Wet Lead Acid
12.0V
24.0V
48.0V
windynation
Lithium
10.5V
9.0V
21.0V
18.0V
42.0V
36.0V
Lithium
12.0V
9.6V
24.0V
19.2V
48.0V
38.4V
05/06/2015