Figure 3-4 Tower-mounting the UPS
A distance of at least 280 mm is recommended between two bases so that the UPS stands
firmly.
----End

3.4 Connecting Power Cables

Connect power cables to the UPS after switching off circuit breakers and securing the UPS.
Reverse battery connection will cause short circuits.
To connect power cables, perform the following steps:
Step 1 Switch off the three circuit breakers that respectively control batteries, loads, and AC input.
Step 2 Remove the busbar protective cover.
Step 3 Connect the ground cable.