UPS2000-G1-(6 kVA–10 kVA)
User Manual
Item
Enviro
nment
Certifi
cation
Issue 05 (2013-07-17)
Voltage
Frequency
Waveform
Switchover time
Overload withstand capability
Output mode
Operating temperature
Storage temperature
Relative humidity
Operation altitude
Acoustical noise
EMC
Safety and regulatory
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
Specifications
UPS2000-G1-6
kVA
220 / 230 / 240 V AC (tolerance ± 2%)
Normal mode: The UPS output phase is the
same as the bypass input phase when
synchronized.
Battery mode: 50 Hz / 60 Hz (tolerance
± 0.5%)
Sine wave (The total harmonic distortion
[THD] at linear loads is less than 3%.)
1 ms for the UPS to switch from the normal
or battery mode to the bypass mode
0 ms for the UPS to switch from the normal
mode to the battery mode
105%–130% rated load: The UPS switches to
the bypass after 10 minutes.
130%–150% rated load: The UPS switches to
the bypass after 1 minute.
≥ 150% rated load: The UPS switches to the
bypass after 1 second.
One busbar and three IEC-C13 sockets are
provided.
0–40° C
–20° C to +55° C (After the UPS has been
stored or transported at –20° C, do not install
it until its temperature has been kept at 0° C
for four hours.)
0%–95% (non-condensing)
≤ 1500 m
When the altitude is greater than 1500 m, the
output capacity should be derated as required
by the GB/T 3859.2.
< 65 dB
Complies with the EN/IEC 60240-2
Complies with the EN/IEC 60240-1
UPS2000-G1-10
kVA
37