Model a built-in i/o: 12 digital inputs, 12 digital outputs, 4 analog inputs, 2 analog outputs
model r built-in i/o: 12 digital inputs, 6 relay outputs, 2 pwm outputs, 4 analog inputs, 2 analog outputs (4 pages)
XL6 Prime Datasheet - Model 2 12 DC In, 6 Relay Out, 4 – 12-bit Analog In MAN1327-21-EN_XL6P_Mod2 Table of Contents User Manual and Add-Ons Backup Battery TECHNICAL SPECIFICATIONS General Specifications Control and Logic User Interface Connectivity CONTROLLER OVERVIEW Part Numbers Overview of OCS Power Wiring Global Part Number HE-XPL1E2...
TECHNICAL SPECIFICATIONS General Specifications User Interface Typical P ower B ack- Display T ype 5.77” V GA T FT ( 450 nit t ypical) 415mA @ 10VDC (4.15W) 191mA @ 24VDC (4.58W) light 100% Resolution 640 x 4 80 Power B acklight @ Color 16-bit ( 65,536) 111mA @ 24VDC (2.66W) Screen ...
CONTROLLER OVERVIEW Overview of OCS Power Wiring NOTE: The Primary Power Range is 10VDC to 30VDC. Primary Power Port Pins Signal Description Ground Frame Ground Input Power Supply Ground Input Power Supply Voltage DC Input / Frame Solid/Stranded Wire: 12-24 awg (2.5-0.2mm) Strip length: 0.28” (7mm) 1. Touchscreen Torque, Terminal Hold-Down Screws: 4.5 – 7 in-lbs 2. Function Keys (0.50 – 0.78 N-m) 3. USB 2.0 “A”: Flash Drive ...
Wiring: Model 2 MODEL 2 SPECIFICATIONS Digital DC Input Analog Inputs, Medium Resolution 12 i ncluding 4 c onfigurable H SC Number o f C hannels Inputs p er M odule inputs Input R anges 0-10VDC, 0 -20mA, 4-20mA Commons ...
NOTE: When using JP2 (A1-A4), each channel can be inde- Digital inputs may be wired in either a Positive Logic or Neg- pendently configured. ative Logic fashion as shown. The setting in the Cscape Hardware Configuration for the Digital Inputs must match Back Panel Torque Ratings the wiring used in order for the correct input states to be registered. No jumper settings are required for XLEe/XLTe. XLE/XLT: 3.0 - 4.0 in-lbs (0.34 - 0.45 N-m) When used as a normal input and not for high speed func- XL4/XL4 Prime: 3.0 - 4.0 in-lbs (0.34 - 0.45 N-m) tions, the state of the input is reflected in registers %I1 – EXL6/XL6 Prime: 3.0 - 4.0 in-lbs (0.34 - 0.45 N-m) %I12. EXLW/ XLW Prime: 3.0 - 3.5 in-lbs (0.34 - 0.40 N-m) XL7/XL7 Prime: 3.0 - 3.5 in-lbs (0.34 - 0.40 N-m) EXL10/XL10 Prime: 3 .0 - 3.5 in-lbs (0.34 - 0.40 N-m) Page 5...
Wiring: Model 2 J1 Wiring - Digital In / Analog In Wiring Details Solid/Stranded Wire: 1 2-24 awg (2.5-0.2mm2). Strip Length: 0 .28” (7mm). Torque, Terminal Hold-Down Screws: 4 .5 – 7 in-lbs (0.50 – 0.78 N-m). BUILT-IN I/O The I/O is mapped into OCS Register space, in three sep- arate areas – Digital/Analog I/O, High-Speed Counter I/O, and High-speed Output I/O. Digital/Analog I/O location is fixed starting at 1, but the high-speed counter and high- speed output references may be mapped to any open register location. NOTE: The 0V terminals are internally connected. Digital and Analog I/O Functions Digital ...
COMMUNICATIONS Serial Communication Dip Switches MJ1/2 Serial Ports MJ1/2 Independent Serial Ports MJ1: RS-232 w/Full Handshaking MJ2: R S-485 Half-Duplex MJ1 PINS MJ2 PINS SIGNAL DIRECTION SIGNAL DIRECTION DIP Switches NAME FUNCTION DEFAULT GROUND GROUND MJ3 RS-485 ON = +5V @ +5V @ Termination Terminated 60mA 60mA ON = Half...
DIMENSIONS & INSTALLATION Dimensions & Panel Cutout Installation Procedure 1. Carefully locate an appropriate place to mount the OCS. Be sure to leave enough room at the top of the unit for insertion and removal of the microSD™ card. 2. Carefully cut the host panel per the diagram, cre- ating a 31.9mm x 175.0mm, with a +1mm/-0mm opening into which the OCS may be installed. If the opening is too large, water may leak into the enclos- ure, potentially damaging the unit. If the opening is too small, the OCS may not fit through the hole without damage. 3. Remove any burrs and or sharp edges and ensure the panel is not warped in the cutting process. 4. Remove all Removable Terminals from the OCS. Insert the OCS through the panel cutout (from the front). The gasket must be between the host panel and the EXL6. 5. Install and tighten the four mounting clips (provided in the box) until the gasket forms a tight seal. NOTE: Max torque is 0.8 to 1.13Nm, or 7 to 10 in-lbs. 6. Reinstall the I /O Removable Terminal Blocks. Con- nect communications cables to the serial port, USB ports, Ethernet port and CAN port as required. ...
This device complies with Part 15 of the FCC Rules. Operation is aging voltage potential between the laptop and controller. subject to the following Ensure the controller a nd laptop are grounded for max- two conditions: imum protection. Consider using a USB isolator due to 1. This device may not cause harmful interference. voltage potential differences as a preventative measure. 2. This device must accept any interference received, includ- ing interference that may cause undesired operation. Technical Support North America 1 (317) 916-4274 (877) 665-5666 www.hornerautomation.com techsppt@heapg.com Europe +353 (21) 4321-266 www.hornerautomation.eu technical.support@horner-apg.com Page 9...