Chapter 3 Rack Mounting; Rack-Mount Installation Procedure - Nortel Contivity 4600 Installing

Hide thumbs Also See for Contivity 4600:
Table of Contents

Advertisement

Chapter 3
Rack Mounting
This chapter describes how to mount the Contivity 4600 into a chassis
rack. Included are standard rack-mounting considerations that Nortel
Networks recommends.

Rack-mount installation procedure

Following are standard rack-mounting considerations that Nortel Networks
recommends you follow:
You must have two people available when installing the rack-mount brackets.
Warning: The Contivity 4600 weighs about 60 pounds and should
always be carried by two people
The maximum recommended ambient temperature is 40 degrees
Centigrade. Additionally, make sure the internal temperature of the rack
does not exceed 40 degrees.
Do not block the power supply vents or otherwise restrict airflow when
installing the switch in a rack.
Make sure that your rack is properly stabilized so that it will not tip over
under the weight of the switch and other devices.
Make sure that the electrical branch circuits are capable of handling the
switch and other units in the rack before installing and powering up the
switch.
Ensure that a reliable Earthing path is maintained in the rack system. The
Switch is intended to be connected to an Earth ground.
Installing the Contivity 4600
39