Watts WFHC 06Z 02 HC RF 24 User Manual page 7

Water floor controller wireless

Advertisement

4.3
Pump Output
There are 2 outputs:
Live contact output (230Vac)
Free contact output
These outputs can be used to trigger:
A zone valve
A pump
A boiler or heat pump
The 2 outputs are triggered when there are a heating or
cooling demand
In the controller if DIP switch 1=local
In the system if DIP switch 1=Global
See 3.3
The delay between the heating or cooling demand and the
pump activation is configurable.
Pump starts 2 minutes after heating or cooling
demand if DIP switch 3=OFF
Pump starts 5 minutes after heating or cooling
demand if DIP switch 3=ON
See 3.3
The purpose it to take account the latency of the actuator.
The delay between the end of the heating or cooling
demand and pump output stop is configurable:
Pump stops 5 minutes after heating or cooling
demand stop if DIP switch 3=OFF
Pump stops 20 minutes after heating or
cooling demand stop if DIP switch 3=ON
See 3.3
The purpose is to dispel the energy.
4.4
Security input
This is a security input (Free contact).
Closed Contact
Opened Contact
When the contact is opened,
The local pump output is stopped
The actuators are closed
The Pump/Drier Led is red blinking
The Heat and Cool led is Red or blue
blinking
If the controller is a sub controller, the
heating or cooling demand is not sent to
the main controller
You can use a contact thermostat for thermal security. You
can install 2 contact thermostats in serial to protect against
both overheating and overcooling.
The product is delivered with a strap on the connector.
No security detection
Overheating or
overcooling detection
7