Address Settings On The Twinsafe Ethercat Box; Mounting; Fig. 5 Rotary Switch For Setting The Twinsafe Address - Beckhoff EP1908 Operating Instructions Manual

Twinsafe ethercat box with 8 fail-safe inputs
Table of Contents

Advertisement

5.2.3

Address settings on the TwinSAFE EtherCAT Box

Fig. 5: Rotary switch for setting the TwinSAFE address
The TwinSAFE address of the box must be set using the three rotary switches at the bottom of the
EP1908-0002 TwinSAFE EP Box. TwinSAFE addresses between 1 and 4095 are available.
Rotary switch
1 (left)
0
0
0
...
0
0
0
...
0
1
1
...
F
TwinSAFE address
Each TwinSAFE address may only be used once within a network!
The address 0 is not a valid address.
5.2.4

Mounting

Protect connectors against soiling
Protect all connections from contamination during module installation!
Protection class IP67 can only be guaranteed if all cables and connectors are connected!
Unused connections must be protected with the appropriate connectors (connector sets see
catalogue)!
The modules are mounted with two M3 screws. The bolts must be longer than 15 mm. The fixing holes are
not threaded. Note when mounting that the overall height is increased further by the fieldbus connections.
EP1908
2 (center)
0
0
0
...
0
1
1
...
F
0
0
...
F
WARNING
Version: 3.0.0
3 (right)
1
2
3
...
F
0
1
...
F
0
1
...
F
Operation
Address
255
256
257
4095
1
2
3
...
15
16
17
...
...
21