Siemens SIMATIC NET RUGGEDCOM RS8000H Installation Manual page 37

Rugged ethernet switches
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
61000-4-6
61000-4-8
61000-4-29
61000-4-11
61000-4-12
61000-4-16
61000-4-17
EC 60255-5
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
28
Test
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
Description
Signal ports
DC Power
ports
AC Power
ports
Earth
ground ports
Enclosure
ports
DC Power
ports
AC Power
ports
Signal ports
DC Power
ports
AC Power
ports
Signal ports
DC Power
ports
DC Power
ports
Signal ports
DC Power
ports
AC Power
ports
Signal ports
DC Power
ports
AC Power
ports
Test Levels
10 V
10 V
10 V
10 V
40 A/m continuous,
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
2.5 kV common, 1 kV
differential mode @ 1 MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
10%
2 kVAC  (Fail-
Safe Relay output)
1.5 kVDC
2 kVDC
5 kV  (Fail-Safe
Relay Output)
5 kV
5 kV
Installation Manual, 11/2022, C79000-G8976-1022-07
Severity
Levels
3
3
3
3
 
 
 
 
3
3
3
4
4
3
 
 
 
 
 
 
RUGGEDCOM RS8000H

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SIMATIC NET RUGGEDCOM RS8000H and is the answer not in the manual?

Questions and answers

Table of Contents