Siemens SIMATIC NET RUGGEDCOM RS8000H Installation Manual page 38

Rugged ethernet switches
Table of Contents

Advertisement

temporary communication loss, while Class 2 requires error-free and interrupted
communications.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
RUGGEDCOM RS8000H
Installation Manual, 11/2022, C79000-G8976-1022-07
IEEE 1613
Clause
9
8
Radiated RFI
7
Transient
Oscillatory
6
HV Impulse
Dielectric
Strength
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
6.2 EMC and Environmental Type Tests
Description
ESD
Enclosure Contact
Enclosure Air
Enclosure ports
Fast
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
Certification
Test Levels
±8 kV
±15 kV
35 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV
±4 kV
2.5 kV common
mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC (Failsafe Relay)
1.5 kVDC
2 kVAC
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% (non-
condensing), 55 °C
(131 °F), 6 cycles
2 g @ 10-150 Hz
30 g @ 11 ms
 
 
 
Class 2
Class 2
29

Advertisement

Table of Contents
loading