Technical Specifications - Unigas RG91 Manual

Microprocessor controlled
Table of Contents

Advertisement

Technical specifications

BURNERS
Output
Light oil rate
Fuel
Viscosity
Density
Oil train pressure inlet
Power supply
Fan motor
Pump motor
Total power consumption
Index of protection
Approx. weight
Operation
Operating temperature
Storage temperature
Working service *
BURNERS
Output
Fuel
Light oil rate
Viscosity
Density
Oil train pressure inlet
Power supply
Electric motor
Pump motor
Total power consumption
Operation
Index of protection
Operating temperature
Storage temperature
Working service
WARNING: Burners are suitable only for indoor operation with a maximum relative humidity of 80%
NOTE: Choosing the nozzle for light oil, consider Hi equal to 42.7 MJ/kg.
RG91
min - max kW
698 - 2093
min - max kg/h
59 - 176
cSt @ 40 °C
3
kg/m
bar max
kW
4
kW
1,1
kW
5,6
kg
220
°C
°C
RG510
min - max kW
1314 - 3953
min - max kg/h
111 - 333
cSt @ 40 °C
3
kg/m
bar max
kW
7,5
kW
1,1
kW
9,1
°C
°C
7
PART I: SPECIFICATIONS
RG92
849 - 2558
72 - 215
Light oil
2 - 7,4
840
4
400V 3N ~ 50Hz
5,5
1,1
7,1
IP40
220
Progressive - Fully modulating
-10 ÷ +50
-20 ÷ +60
Continuous
RG515
RG520
1628 - 4884
2326 - 6977
Light oil
137 - 411
196 - 588
2 - 7,4
840
4
400V 3N ~ 50Hz
11
15
1,5
1,5
13
17
Progressive - Fully modulating
IP40
-10 ÷ +50
-20 ÷ +60
Continuous
RG93
550 - 4100
46 - 345
7,5
1,1
9,1
230
RG525
2000 - 8000
169 - 674
18,5
3
22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rg92Rg93Rg510Rg515Rg520Rg525

Table of Contents