8 SPECIAL POSITIONS
8.1
Ignition position
The ignition point is independent from the other curve points of the air/fuel ratio curve.
As far as dual fuel burners, the ignition point set for the gas operation does not depend on the one set for the oil operation. LMV5x allow two different
ignition position for gas mode and oil mode.
The burner is provided with a factory-set ignition point, to make easier the first ignition procedure by the Service Centre.
The air actuator at the ignition point, is factory set at a 6°/7° opening, while the gas actuator is set at 12°/15°. In case of burner provided with VSD, it is
suggested to set ignition at 100% VSD frequency.
Following the below route access to the programming levels of the menu by means the Esc
1st level
2nd level
Params & Display
RatioControl
8.2
Prepurge position
Following the same route up to the 4th level, choose the pre-purge position of the servomotors
8.3
Home position
Following the same route up to the 4th level, choose the home position of the servomotors
8.4
Postpurge position
Following the same route up to the 4th level, choose the postpurge position of the servomotors
3rd level
4th level
GasSettings
OilSettings
Special Positions
5th level
IgnitionPos
HomePos
PrepurgePos
PostpurgePos
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux 1
IgnitionPosAux 2
IgnitionPosAux 3
IgnitionPosVSD
25
6th level
Description
Menu level for making the
para- meter set- tings
Choose according to the fired
fuel.
Set the proper position
Set the proper position
Set the proper position
Set the proper position
Set the proper position
Set the proper position