6.4
Setting the setpoint and the burner and the PID operative band.
6.4.1
Set-point
To set the temperature set-point value, that is the generator operating temperature; proceed as follows.
1st level
2nd level
Params & Display
LoadController
It appears the below screen:
SetPointW1
Curr: 90°
New: 90°
After setting the set-point it is necessary t oset the operation range of the burner. See paragraph SD_ModON e SD_Mod Off
6.4.2
SD_ModON e SD_Mod Off
Once the temperature set-point W1 is stored, set the burner switch-on (SDon) and the switch-off (SDoff) point:
To set these values, choose the item SD_ModOn (SDOn), by scrolling down the "Load controller" menu with the arrow keys and press ENTER:
1st level
2nd level
Params & Display
SD:ModOn
SD:ModOff
the display will show:
SD_ModOn
Curr: 1.0%
New: 1.0%
The SD_ModOn default value for this parameter is1% that is, the burner will light again at a temperature 1% lower than the set-point.
Change value, if needed, by means of the arrow keys; press ENTER to confirm and the press ESC to exit. Press only ESC to exit without changing.
Now choose SD_ModOff always scrolling down the Load Controller menu, by means of the arrow keys, and press ENTER.
3rd level
4th level
ControllerParam
Curr: it shows the current set-point; use the arrows keys to change it.
New: it is the new set value. Enter to confirm, otherwise exit without changing by
pressing ESC.
Press ESC one more time to exit the set-point programming mode.
3rd level
4th level
5th level
6th level
5th level
6th level
Menu level for
Params &
making the
Display
t
General
configuration of
the load
General
configuration of
SD_ModOff
Curr: 10.0%
New: 10.0%
21
Description
Menu level for making the parameter
settings
General configuration of the load
controller
Controller parameters
SD_ModOff = above this set value
the burner shut down
SD_ModOff = below this set value
the burner restar
servomotors open (means burner
output increase)
servomotors close (means burner
output decrease)
Description
SD:ModOn
SD:ModOff