Under the actuator settings you can configure the settings described in the following.
Pos.
[1]
[2]
[3]
[4]
[5]
[6]
 
Product manual 2CKA001373B8563
Description
Device name
An independent designation for the device can be allocated via the text field.
Position
By tapping on the drop-down menu you can assign a position to the device in the
building structure you defined (e.g. assignment to a room on a certain floor).
Incoming links
Via this function you can also see for which devices a link has been created.
The pairing can be deleted again by tapping on the dustbin icon.
Authorizations
Menu item "Authorizations" is used to specify whether a user with installer authorization
is required for the reconfiguration of the actuator.
In addition, you can nevertheless assign users with read rights the authorization to
switch this actuator.
Function
The current function of the actuator is displayed via menu item "Function". You can
change the function if necessary.
Heating mode
Heating mode with additional heating
Cooling mode
Auto. heating/cooling mode (for 2-pipe systems)
Two valves for heating and cooling (only 4-pipe systems)
Parameters
Fan mode
Selection of the fan mode.
Night mode
Activation and selection of the night mode.
Fan stage upon reach of setpoint
With this setting, you specify whether the fan should remain at the set level after a
manual adjustment, whether it should be switched off or whether it should switch to
automatic mode.
Behaviour during faults (%)
Use the slider to specify a control value for the valve opening in the event of faults.
Fan mode
Select "Step switch" or "2-way circuit" for the fan.
Fan changeover delay (ms)
Setting the time the fan must be deactivated between switchover of levels for the two-
way circuit, to prevent damage to the fan.
Commissioning