Ideal Heating ECOMOD AHP60 26 kW Installation And Servicing page 6

Air/water monobloc heat pump
Table of Contents

Advertisement

1.2.2.
Unpacking the unit
Acceptance
With the carrier present, carefully check the general appearance of the packaging and the
appliances. Check that the outdoor appliance has not been placed in a horizontal position.
In the event of disagreement, write to the carrier within 48 hours mentioning all reserves and
send a copy of this letter to the After Sales Department.
Before unpacking the appliance, check that there are no refrigerant leaks using a suitable
detector. Check that there are no ignition sources near the unit.
Smoking is forbidden near to the unit.
1.2.3.
Safety recommendations related to the presence of the R32 refrigerant
The handling and installation of this outdoor appliance must only be performed by personnel
that are duly trained, qualified and authorised to carry out these operations, according to the
laws, directives and standards applicable in each country.
The EN378:2016 standard defines the framework of requirements to be met to manage each
potential risk at each stage of the machine's life cycle. This standard was also used to design
this machine.
In the absence of local building codes or safety standards, the installation and maintenance of
the machine may follow the elements outlined in this standard; in particular, it is the responsibility
of the installer and personnel performing operations on this machine to perform a risk analysis
prior to any installation and work on the machine.
The elements indicated below are not exhaustive given the diversity of the possible
installations and interventions; they cannot be considered as an undertaking as to the
responsibility of Ideal Heating. These elements cannot replace a risk analysis, which
remains the responsibility of the installer and the personnel working on the machines.
Designation
Main dangers:
Specific dangers:
General information
Inhalation:
Contact with the eyes:
Contact with the skin:
Extinguishers:
Specific dangers:
Specific methods:
6 / 74
R32.
INDICATION OF DANGERS
Asphyxia.
The rapidity of evaporation can cause burns.
EMERGENCY MEASURES
Do not give anything to persons who have fainted.
Take the person to fresh air.
Use oxygen or artificial respiration if required.
Do not administer adrenaline or similar substances.
Rinse thoroughly with water for at least 15 minutes and seek
medical attention.
Rinse thoroughly with water for at least 15 minutes. Apply a sterile
gauze.
Remove contaminated clothing immediately.
FIRE PREVENTION MEASURES
Water spray, dry powder.
Rupture or explosion of the recipient.
Cool down the recipients by spraying with water from a safe
position. If possible, stop the product from leaking. If possible, use
a water spray to hose down the smoke. Move the recipients well
clear of the fire zone if possible without taking risks.
00U07352250-A_EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecomod ahp60 32 kw

Table of Contents