Sensor Menu [Tp]; Error Menu [Err]; Operating Hours Menu [Ohr]; Parameter Menu [Par] - Ideal Heating ECOMOD AHP60 26 kW Installation And Servicing

Air/water monobloc heat pump
Table of Contents

Advertisement

5.3. Sensor menu [TP]

Access the PSS menu to enter the maintenance technician password "195" and to activate
access to a higher level. Once you have fully exited the menus,
the password privileges are lost and the password needs to be entered once again.

5.4. Error menu [Err]

This menu is only displayed if there are errors in progress. It allows all of the ongoing errors to
be viewed. If this is a multi-circuit unit, then the errors are separated by circuit. (The label ALx
provides access to the errors of the number x circuit).

5.5. Operating hours menu [OHR]

OH1: Compressor operating hours
OHP: Pump operating hours
Access the PSS menu to enter the maintenance technician password "195" and to activate
access to a higher level. Once you have fully exited the menus,
the password privileges are lost and the password needs to be entered once again.

5.6. Parameter menu [Par]

DESCRIPTION
Configuration
Not used
Not used
Not used
Not used
Not used
Not used
In CnF parameter H84, enter 21 to activate the heat pump de-icing signalling output
In CnF parameter H46, enter 25 to activate the silent ventilation function input
In CnF parameter H85, enter 47 to activate the heat pump alarm output
01-07-2022
LABEL
T01
Inlet water temperature
T02
Outlet water temperature
T03
Compressor suction temperature
T04
Compressor discharge temperature
T05
External air temperature
T06
- not used -
T07
- not used -
T09
Low pressure sensor
T10
High pressure sensor
GROUP IDENTIFICATION CODE
CnF
CP
ALL
rE
PUP
Fro
dFr
AHP60 26/32 kW - Installation, Use and Maintenance
SENSOR
PARAMETER SUMMARY
H01-
C01-
A01-
b01-
P01-
r01-
d01-
51 / 74