Summary of Contents for SystemAir SYSHP MINI SPLIT 06-16 + TANK
Page 1
Air Conditioning SYSHP MINI SPLIT 06-16 + TANK Mini Heat Pump Split Series 7,0 to 14,0 kW 6,35 to 16,0 kW Engineering Data Manual...
Page 2
CONTENTS Part 1 General Information ..................3 Part 2 Engineering Data ..................11 Part 3 Field Settings .....................45...
Page 4
Part 1 General Information Air-to-Water HP Split System ................4 Unit Capacities ....................6 Nomenclature ....................6 System Design and Unit Selection ..............9...
Air-to-Water HP Split System 1.1 System Schematic Hot water Water supply Radiator Mixing station Floor heating Buffer tank Indoor unit Outdoor unit It is an integrated air-to-water heat pump system which is one-stop solution for space heating, space cooling and domestic hot water.
Page 6
1.2 System Configurations It can be configured to run with the electric heater either enabled or disabled and can also be used in conjunction with an auxiliary heat source such as a boiler. The chosen configuration affects the size of heat pump that is required. Three typical configurations are described below. Configuration 1: Heat pump only ▪...
Nomenclature 3.1 Outdoor unit SYSHP MINI SPLIT Power Supply R: 3-phase, 380-415V, 50Hz Q: 1-phase, 220-240V, 50Hz Capacity in kW ODU: outdoor unit Split version Model...
Page 9
3.2 Hydro module with water tank SYSHP MINI SPLIT TANK Power Supply Q: 1-phase, 220-240V, 50Hz Capacity in kW TANK: indoor unit Split version Model...
System Design and Unit Selection 4.1 Selection procedure Step 1: Total heat load calculation Calculate conditioned surface area Select the heat emitters (type, quantity, water temperature and heat load) Step 2: System configuration Decide whether to include AHS and set AHS’ s switching temperature Decide whether backup electric heater is enabled or disabled Step 3: Selection of outdoor units Determine required total heat load on outdoor units...
Page 11
4.2 Heat Pump Leaving Water Temperature (LWT) Selection The recommended design LTW ranges for different types of heat emitter are: ▪ For floor heating: 30 to 35⁰ C ▪ For fan coil units: 40 to 45⁰ C ▪ For low temperature radiators: 40 to 50⁰ C 4.3 Optimizing System Design To get the most comfort with the lowest energy consumption with the Heat Pump , it is important to take account of the following considerations:...
Page 13
Specifications 1.1 Outdoor Unit Model name SYSHP MINI SPLIT ODU 04 Q SPLIT ODU 06 Q SPLIT ODU 08 Q SPLIT ODU 10 Q Indoor Unit Model SYSHP MINI SPLIT TANK 190 Q Capacity 4.25 6.20 8.30 10.0 A7W35 Rated input 0.82 1.24 1.60...
Page 14
Drain connection DN32 Outdoor unit sound Power Level(3) Heating °C Ambient temperature Cooling °C range Domestic hot water °C Power supply V/Ph/Hz 220-240/1/50 Rated input 3095 Rated current 13.5 Type Stainless steel Material SUS 316L Water Volume Maximum water temperature(Disinfection °C DHW Tank mode)
Page 15
Model name SYSHP MINI SPLIT ODU 04 Q SPLIT ODU 06 Q SPLIT ODU 08 Q SPLIT ODU 10 Q Indoor Unit Model SYSHP MINI SPLIT TANK 240 XL Q Capacity 4.25 6.20 8.30 10.0 A7W35 Rated input 0.82 1.24 1.60 2.00 5.20...
Page 16
Drain connection DN32 Outdoor unit sound Power Level(3) Heating °C Ambient temperature Cooling °C range Domestic hot water °C Power supply V/Ph/Hz 220-240/1/50 Rated input 3095 Rated current 13.5 Type Stainless steel Material SUS 316L Water Volume Maximum water temperature(Disinfection °C DHW Tank mode)
Page 17
Model name SYSHP MINI SPLIT ODU 12 Q SPLIT ODU 14 Q SPLIT ODU 16 Q Indoor Unit Model SYSHP MINI SPLIT TANK 240 Q Capacity 12.1 14.5 16.0 A7W35 Rated input 2.44 3.09 3.56 4.95 4.70 4.50 Capacity 12.3 14.2 16.0 A7W45...
Page 18
Drain connection DN32 Outdoor unit sound Power Level(3) Heating °C Ambient temperature Cooling °C range Domestic hot water °C Power supply V/Ph/Hz 220-240/1/50 Rated input 3095 Rated current 13.5 Type Stainless steel Material SUS 316L Water Volume Maximum water temperature(Disinfection °C DHW Tank mode)
Page 19
Model name SYSHP MINI SPLIT ODU 12 R SPLIT ODU 14 R SPLIT ODU 16 R Indoor Unit Model SYSHP MINI SPLIT TANK 240 Q Capacity 12.1 14.5 16.0 A7W35 Rated input 2.44 3.09 3.56 4.95 4.70 4.50 Capacity 12.3 14.2 16.0 A7W45...
Page 20
Drain connection DN32 Outdoor unit sound Power Level(3) Heating °C Ambient temperature Cooling °C range Domestic hot water °C Power supply V/Ph/Hz 220-240/1/50 Rated input 3095 Rated current 13.5 Type Stainless steel Material SUS 316L Water Volume Maximum water temperature(Disinfection °C DHW Tank mode)
Page 21
2 Dimensions 2.1 Outdoor Unit SYSHP MINI SPLIT ODU 04, 06 Q SYSHP MINI SPLIT ODU 08, 10 Q SYSHP MINI SPLIT ODU 12, 14, 16 Q SYSHP MINI SPLIT ODU 12, 14, 16 R...
Page 22
2.2 Hydro module Model A(mm) B(mm) C(mm) D(mm) SYSHP MINI SPLIT TANK 190 Q 1775 1748 1682 SYSHP MINI SPLIT TANK 240 XL Q 2034 2007 1942 1045 SYSHP MINI SPLIT TANK 240 Q 2034 2007 1942 1045...
Page 23
Operating Limits Heating operating limits Cooling operating limits Domestic hot water operating limits Abbreviations: T4: Outdoor temperature (°C) T1: Leaving water temperature (°C) Notes: If IBH/AHS setting is valid, only IBH/AHS turns on; If IBH/AHS setting is invalid, only heat pump turns on Water flow temperature drop or rise interval IBH/AHS only...
Page 38
Performance curves in domestic hot water production 15°C~45°C 15°C~50°C 15°C~55°C SYSHP MINI SPLIT ODU 04, 06 Q + SYSHP MINI SPLIT TANK 190 Q SYSHP MINI SPLIT ODU 04, 06 Q + SYSHP MINI SPLIT TANK 240XL Q Heat up Heat up -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 -20 -15 -10 -5 0...
Page 39
15°C~45°C 15°C~50°C 15°C~55°C SYSHP MINI SPLIT ODU 08, 10 Q + SYSHP MINI SPLIT TANK 190 Q SYSHP MINI SPLIT ODU 08, 10 Q + SYSHP MINI SPLIT TANK 240XL Q Heat up Heat up -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45...
Page 40
15°C~45°C 15°C~50°C 15°C~55°C SYSHP MINI SPLIT ODU 12, 14, 16 Q, R + SYSHP MINI SPLIT TANK 240 Q Heat up -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 T4/℃ Heating Capacity 10000 9000 8000 7000 6000...
Page 41
Hydronic Performance Hydro module with 190L water tank Water flow (m3/h) Hydro module with 240L water tank Water flow (m3/h)
Page 42
Sound Levels 6.1 Overall Model name SYSHP MINI SPLIT ODU 04 Q SYSHP MINI SPLIT ODU 06 Q SYSHP MINI SPLIT ODU 08 Q SYSHP MINI SPLIT ODU 10 Q SYSHP MINI SPLIT ODU 12 Q SYSHP MINI SPLIT ODU 14 Q SYSHP MINI SPLIT ODU 16 Q SYSHP MINI SPLIT ODU 12 R SYSHP MINI SPLIT ODU 14 R...
Page 43
6.2 Octave Band Levels SYSHP MINI SPLIT ODU 04 Q + SYSHP MINI SPLIT TANK 190 Q octave band levels Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ NR-90 NR-80 Outdoor air temperature 35⁰C DB;...
Page 44
SYSHP MINI SPLIT ODU 08 Q + SYSHP MINI SPLIT TANK 190 Q octave band levels Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ NR-90 NR-80 NR-70 Outdoor air temperature 35⁰C DB;...
Page 45
SYSHP MINI SPLIT ODU 14 Q, R + SYSHP MINI SPLIT TANK 240 Q octave band levels Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ NR-90 NR-80 Outdoor air temperature 35⁰C DB;...
Page 46
Part 3 Field Settings User Interface Field Settings ................46 Operation parameter Checking ..............65 Network Configuration Guidelines ..............66 Climate Related Curves .................71...
Page 47
User Interface Field Settings 8.1 Introduction During installation, the Heat Pump settings and parameters should be configured by the installer to suit the installation configuration, climate conditions and end-user preferences. The relevant settings are accessible and programmable through the FOR SERVICEMAN menu on the Heat Pump user interface. The user interface is integrated design in the hydro module. Keys Function MENU...
Page 49
8.3 FOR SERVICEMAN Menu FOR SERVICEMAN allows installers to input the system configuration and set the FOR SERVICEMAN password screen system parameters. To enter FOR SERVICEMAN, go to MENU > FOR SERVICEMAN. Enter the password, using ◄ ► to navigate between digits and using ▼ ▲ to adjust the numerical values, and then press OK.
Page 50
Only when the space heating/cooling is OFF will the heat pump operate to heat domestic water. DHW PUMP sets whether or not the DHW pump is controlled by the Heat Pump Split unit. If the DHW pump is to be controlled by the Heat Pump Split, select YES.
Page 51
T4_TBH_ON sets the ambient temperature above which the immersion heater will not be used. t_TBH_DELAY sets the delay between the compressor starting and the immersion heater being turned on. T5S_DI sets the DHW tank disinfection operation target temperature. Caution: during the disinfection operation (duration: t_DI_ MAX) the domestic hot water temperature at the hot water taps will at times be equal to the value set for T5S_DI.
Page 52
1.5 COOL MODE SETTING Menu MENU > FOR SERVICEMAN > COOL MODE SETTING COOL MODE SETTING menu In COOL MODE SETTING the following parameters should be set. COOL MODE enables or disables cooling mode. For installations with space cooling terminals, select YES to enable cooling mode. For installations without space cooling terminals, select NON to disable cooling mode.
Page 53
T4C1 sets the ambient temperature 1 of automatic setting curve for cooling mode. T4C2 sets the ambient temperature 2 of automatic setting curve for cooling mode. ZONE1 C-EMISSION sets the emission type of zone1 for cooling mode. ZONE2 C-EMISSION sets the emission type of zone2 for cooling mode. 1.6 HEAT MODE SETTING Menu MENU >...
Page 54
t_INTERVAL_H sets the heating mode compressor re-start delay. When the compressor stops running, it will not re-start until at least t_INTERVAL_H minutes have elapsed. T1SetH1 sets the temperature 1 of automatic setting curve for heating mode. T1SetH2 sets the temperature 2 of automatic setting curve for heating mode. T4H1 sets the ambient temperature 1 of automatic setting curve for heating mode.
Page 55
1.8 TEMP. TYPE SETTING Menu MENU > FOR SERVICEMAN > TEMP. TYPE SETTING TEMP. TYPE SETTING menu The TEMP. TYPE SETTING is used for selecting whether the water flow temperature or room temperature is used to control the ON/OFF of the heat pump. When ROOM TEMP.
Page 56
Set DOUBLE ZONE to YES and set ROOM TEMP. to NON; Set WATER FLOW TEMP. to YES or NON Homepage (zone 1) Addition page (zone 2) If set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON, the following page will be displayed.
Page 57
1.10 OTHER HEATING SOURCE Menu 1.10.1 OTHER HEATING SOURCE menu overview MENU > FOR SERVICEMAN > OTHER HEATING SOURCE OTHER HEATING SOURCE menu In OTHER HEATING SOURCE the following parameters should be set. Backup electric heater is optional. dT1_IBH_ON sets the temperature difference between the heat pump’s leaving water set temperature (T1S) and the heat pump’s leaving water temperature (T1) above which the backup electric heater heating element(s) are on.
Page 58
1.11 HOLIDAY AWAY SETTING Menu MENU > FOR SERVICEMAN > HOLIDAY AWAY SETTING The HOLIDAY AWAY SETTING menu settings are used to set the outlet water HOLIDAY AWAY SETTING menu temperature to prevent water pipes freezing when away from home in cold weather seasons.
Page 59
1.14 TEST RUN 1.14.1 TEST RUN Menu overview MENU > FOR SERVICEMAN > TEST RUN TEST RUN is used to check that the valves, air purge function, circulation pump, space cooling mode, space heating mode and DHW mode are all operating correctly. TEST RUN start screen and TEST RUN menu During test run, all buttons except OK are invalid.
Page 60
1.14.3 AIR PURGE operation MENU > FOR SERVICEMAN > TEST RUN > AIR PURGE Once installation is complete it is important to run the air purge function to remove any air which may be present in the water piping and which could cause malfunctions during operation. AIR PURGE operation The AIR PURGE operation is used to remove air from the water piping.
Page 61
1.14.6 HEAT MODE RUNNING operation The HEAT MODE RUNNING operation is used to check the operation of the system HEAT MODE RUNNING display in space heating mode. During the HEAT MODE RUNNING operation the Heat Pump Split unit leaving water set temperature is 35°C.
Page 62
1.15 SPECIAL FUNCTION Special functions menu 1.15.1 SPECIAL FUNCTION menu overview MENU > FOR SERVICEMAN > SPECIAL FUNCTION SPECIAL FUNCTION is used to pre-heating floor and drying up floor once installation is complete or the first time start up the unit or restart the unit after a long time stop.
Page 63
Preheating for floor screens 1.15.3 FLOOR DRYING UP FLOOR DRYING UP menu MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR DRYING UP For newly-installed under-floor heating systems, floor drying up mode can be used to remove moisture from the floor slab and subfloor to prevent warping or rupture of the floor during floor heating operation.
Page 64
1.16 AUTO RESTART AUTO RESTART menu MENU > FOR SERVICEMAN > AUTO RESTART AUTO RESTART sets whether or not the unit re-applies the user interface settings when the power returns following a power failure. Select YES to enable auto restart or NON to disable auto restart.
Page 65
SOLAR INPUT sets whether solar control signal is connected to hydronic PCB. (0=NON; 1=CN18; Tsolar 2=CN11SL1SL2) F-PIPE LENGTH sets the length of refrigerant pipes between outdoor unit and indoor unit. RT/Ta_PCB sets whether hydronic adapter board is valid. Pump silent mode can decrease water pump maximum output by 5% in order to decrease the noise of heat pump. 1.19 HMI ADDRESS SET MENU >...
Page 66
Operation parameter Checking MENU > OPERATION PARAMETER This menu is for installer or service engineer reviewing the operation parameters. There are nine pages for the operating parameter as following Operation parameter...
Page 67
Network Configuration Guidelines The wired controller realizes intelligent control with a built-in WIFI module, which receives control signal from the APP. Before connecting the WLAN, please check for it if the router in your environment is active and make sure that the wired controller is well-connected to the wireless signal.
Page 68
Click on Sign Up and create a new account if you have never created an account of MSmartLife before. If you have already created an account before, login with the email and password. 3.3 Add device and login to home Wi- Fi Click on Add Device to add your Heat Pump Water Heater...
Page 69
Select the Central Water Heater Select the Wi-Fi in your home and type in the password for this Wi-Fi Follow the instructions, refer to 3.4 Wired Controller Setting 1. Click the “MENU” button The App will automatically find on the wired controller, select out the controller, here the “WLAN SETTING”...
Page 70
3.4 Wired Controller Setting Go to “MENU”> “WLAN SETTING”> “AP MODE”. Press “OK” to activate the WLAN. Select YES, press OK to select AP mode. Select AP Mode correspondingly on the mobile device and continue the follow-up settings according to the APP prompts. During the Wireless distribution process, the LCD icon flashes to indicate that the network is being deployed.
Page 71
Name can be changed Go Back to the App , it will take Click on “Complete” , once the some time for the app to finish Account binding is finished 3.4.2 Finishing up It will show the Status as Online. Enter the device to control its settings...
Page 72
Climate Related Curves The climate related curves can be selected in the user interface, MENU > PRESET TEMPERATURE > WEATHER TEMP. SET. WEATHER TEMP.SET menu The curves for heating mode and ECO heating mode are the same but the default curve is curve 4 in heating mode, while in ECO mode, the default curve is curve 6.
Page 73
Low temperature curves for cooling mode T1S(℃) Curve 1 Curve 2 Curve 3 Curve 4 Curve 5 Curve 6 Curve 7 Curve 8 T4(℃) Notes: 1. It only has the curves of the high temperature setting for cooling, if the high temperature is set for cooling. 2.