Insulating The Branch Joint - Samsung AM CXV Series Installation Manual

Table of Contents

Advertisement

Pipe insulation
• The insulation of the gas and liquid pipes can be in contact with each
other but they should not press excessively against each other.
• When the gas side and liquid side pipes are contacting each other,
increase the thickness of the insulation by one grade.
Insulator
Gas pipe
Insulating pipes connected behind the EEV kit
• When installing the gas side and liquid side pipes, leave at least
10mm of space.
• When the gas side and liquid side pipes are contacting each other,
increase the thickness of the insulation by one grade.
10mm (0.4inch)
Gas pipe
CAUTION
• Install the insulation without any gaps or cracks and use
adhesive on the connection part of it to prevent moisture from
entering.
• Bind the refrigerant pipe with insulation tape if it is exposed to
outside sunlight. (When binding the pipe with finishing tape,
be careful not to reduce the thickness of the insulation.)
• Install the refrigerant pipe respecting that the insulation does
not get thinner on the bent part or hanger of pipe.
• When the thickness of insulation is reduced, reinforce the
reduced thickness with additional insulation.
Additional Insulator
Insulate the distribution header
• Fix the distribution header with a cable tie and cover the
connected part.
• Insulate the distribution header and the welded part and wrap
the connected part with an adhesive insulation tape to prevent
dew formation.
42
English
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 42
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 42
Insulating pipes
Insulator
Liquid pipe
10mm (0.4inch)
10mm (0.4inch)
Liquid pipe
Hanger
a
Insulator for
refrigerant pipe
a x 3
Adhesive insulation tape
Insulate the refrigerant
Insulate the
pipe
distribution header
Insulate after welding a stopper
Adhesive insulation tape
• Fix the distribution header with a hanger after insulating it.

Insulating the branch joint

• Tightly attach the insulator, provided with the branch joint,
to the separately purchased insulator. Wrap the connected
part with an insulator (separately purchased item) that has
thickness of at least 10mm (0.4inch).
• Use an insulator that resist heat up to 120℃ (248℉). Wrap the
branch joint with an insulation that has thickness of at least
10mm (0.4inch).
Pipe insulator
(Separately
Provided
purchased item)
Insulator
Fix securely
without any gap.
Branch
joint
150mm (6inch)
Thickness of the insulator (Separately purchased item) should be
thicker than 10mm.
Insulation tape (Separately purchased item)
Pipe
Pipe insulator (Separately purchased item)
※ Attach the adhesive insulation tape to the pipe, as shown in
the picture, after insulating the pipe.
Insulation
Fix securely without any gap.
Pipe insulator
(Separately
purchased item)
2022-09-13 오전 9:34:21
2022-09-13 오전 9:34:21