Branch Joint; Y-Joint; Distribution Header - Samsung DVM S Series Installation Manual

Table of Contents

Advertisement

33.6 kW
40.0 kW
61.6 kW
(1)
(2)
(C)
(A)
(B)
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch.
❇ However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe connected to the outdoor unit
(D), apply the pipe size (D).

1) Y-joint

Classification
Y-joint (E)

2) Distribution header

Classification
Distribution header (E)

Branch joint

Branch joint between outdoor units (C)
(D)
Y-joint for outdoor unit (C)
(3)
First branch joint (D)
(E)
Make a selection according to outdoor unit capacity.
Classification
Y-joint (D)
Model name
MXJ-YA1509M
MXJ-YA2512M
MXJ-YA2812M
MXJ-YA2815M
MXJ-YA3419M
MXJ-YA4119M
MXJ-YA4422M
Model name
MXJ-HA2512M
MXJ-HA3115M
MXJ-HA3819M
Classification
Model name
MXJ-TA3419M
MXJ-TA4122M
Outdoor unit capacity (kW)
40.0 kW and below
40.1 kW ~ 45.0 kW
45.1 kW ~ 67.2 kW
67.3 kW ~ 95.2 kW
95.3 kW ~ 135.2 kW
Over 135.2 kW
Specification (kW)
135.2 kW and below
Over 135.2 kW
Model name of the
branch joint
MXJ-YA2512M
MXJ-YA2812M
MXJ-YA2815M
MXJ-YA3419M
MXJ-YA4119M
MXJ-YA4422M
Specification (kW)
15.0 kW and below
15.1 kW ~ 40.0 kW
40.1 kW ~ 45.0 kW
45.1 kW ~ 70.3 kW
70.4 kW ~ 98.4 kW
98.5 kW ~ 135.2 kW
Over 135.2 kW
Specification (kW)
45.0 kW and below (for 4 rooms)
70.3 kW and below (for 8 rooms)
70.4 kW ~ 135.2 kW
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvm s am080fxvaghDvm s am fxvagr seriesDvm s am100fxvaghDvm s am120fxvaghDvm s am160fxvaghDvm s am140fxvagh ... Show all

Table of Contents