Grounding Work - Samsung AM CXV Series Installation Manual

Table of Contents

Advertisement

Electrical wiring work

Grounding work

Grounding must be done by a qualified installer for your safety.
Grounding the power cable
• The standard of grounding may vary according to the rated voltage and installation place of the air conditioner.
• Ground the power cable according to the following table.
Installation place
High humidity
Average humidity
Low humidity
Note 1) About grounding work 3.
• Grounding work must be done by an expert (with qualification).
• Check if the grounding resistance is lower than 100Ω. When installing an earth leakage breaker (that can cut the electric circuit within
0.5 second in case of a short circuit), allowable grounding resistance should be 30~500Ω.
Note 2) Grounding at dry place
• The grounding resistance should be lower than 100Ω. Even in worst case, grounding resistance should be lower than 250Ω.
Performing the grounding work
• Use a rated grounding cable by referring to the specification of the electric cable for the outdoor unit.
※ When using the exclusive grounding terminal (When the
grounding terminal is already built on the house)
38
English
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 38
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 38
Power condition
Voltage to ground is lower than 150V
Perform grounding work 3.
Perform grounding work 3, if possible, for your safety.
Exclusive
grounding terminal
Must perform the grounding work 3.
(Including the case where earth leakage breaker is installed)
Note 1)
Must perform the grounding work 3. 
(Including the case where earth leakage breaker is installed)
Note 2)
※ When using grounding of the switch board
Voltage to ground is over 150V
Note 1)
Note 1)
Distributing
board
2022-09-13 오전 9:34:19