Technical Data - ABB Relion 670 Series Product Manual

Busbar protection customized
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Busbar protection REB670
Customized
Product version: 1.2

20. Technical data

General
Definitions
Reference value
The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range
The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range
The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Energizing quantities, rated values and limits
Analog inputs
Table 3. TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Current
Operative range
Permissive overload
Burden
Ac voltage
Operative range
Permissive overload
Burden
Frequency
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Table 4. MIM - mA input module
Quantity:
Input resistance
Input range
Power consumption
each mA-board
each mA input
32
Rated value
I
= 1 or 5 A
r
(0-100) x I
r
4 × I
cont.
r
*)
100 × I
for 1 s
r
< 150 mVA at I
= 5 A
r
< 20 mVA at I
= 1 A
r
U
= 110 V
r
(0–340) V
420 V cont.
450 V 10 s
< 20 mVA at 110 V
f
= 50/60 Hz
r
Rated value:
R
= 194 Ohm
in
± 5, ± 10, ± 20mA
0-5, 0-10, 0-20, 4-20mA
£ 2 W
£ 0.1 W
1MRK505273-BEN D
Nominal range
(0.2-40) × I
r
0.5–288 V
± 5%
Nominal range:
-
-
-
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents