ABB Relion 670 Series Product Manual page 64

Busbar protection customized
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Busbar protection REB670
Customized
Product version: 1.2
Table 78. IRIG-B
Quantity
Number of channels IRIG-B
Number of channels PPS
Electrical connector:
Electrical connector IRIG-B
Pulse-width modulated
Amplitude modulated
– low level
– high level
Supported formats
Accuracy
Input impedance
Optical connector:
Optical connector PPS and IRIG-B
Type of fibre
Supported formats
Accuracy
64
Rated value
1
1
BNC
5 Vpp
1-3 Vpp
3 x low level, max 9 Vpp
IRIG-B 00x, IRIG-B 12x
+/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
100 k ohm
Type ST
62.5/125 μm multimode fibre
IRIG-B 00x, PPS
+/- 2μs
1MRK505273-BEN D
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents