Busbar protection REB670
Customized
Product version: 1.2
Control
Table 42. Autorecloser SMBRREC
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5
Extended autorecloser open time
Autorecloser maximum wait time for sync
Maximum trip pulse duration
Inhibit reset time
Reclaim time
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle
Circuit breaker closing pulse length
CB check time before unsuccessful
Wait for master release
Wait time after close command before proceeding to next shot
52
1MRK505273-BEN D
Range or value
Accuracy
1 - 5
-
(0.000-60.000) s
± 0.5% ± 10 ms
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s