ABB Relion 670 Series Product Manual page 55

Busbar protection customized
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Busbar protection REB670
Customized
Product version: 1.2
Table 48. Current sequence component measurement CMSQI
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Table 49. Voltage sequence measurement VMSQI
Function
Voltage positive sequence, U1
Voltage zero sequence, 3U0
Voltage negative sequence, U2
Phase angle
Table 50. Supervision of mA input signals
Function
mA measuring function
Max current of transducer to
input
Min current of transducer to
input
Alarm level for input
Warning level for input
Alarm hysteresis for input
Table 51. Event counter CNTGGIO
Function
Counter value
Max. count up speed
ABB
Range or value
(0.1–4.0) × I
r
(0.1–1.0) × I
r
(0.1–1.0) × I
r
(0.1–4.0) × I
r
Range or value
(10 to 300) V
(10 to 300) V
(10 to 300) V
(10 to 300) V
Range or value
± 5, ± 10, ± 20 mA
0-5, 0-10, 0-20, 4-20 mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(-20.00 to +20.00) mA
(0.0-20.0) mA
Range or value
0-100000
10 pulses/s (50% duty cycle)
Accuracy
± 0.2% of I
at I ≤ 0.5 × I
r
r
± 0.2% of I at I > 0.5 × I
r
± 0.2% of I
at I ≤ 0.5 × I
r
r
± 0.2% of I at I > 0.5 × I
r
± 0.2% of I
at I ≤ 0.5 × I
r
r
± 0.2% of I at I > 0.5 × I
r
± 0.5° at 0.2 × I
< I < 0.5 × I
r
± 0.2° at 0.5 × I
≤ I < 4.0 × I
r
Accuracy
± 0.3% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
± 0.3% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
± 0.3% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
± 0.3° at U ≤ 50 V
± 0.2° at U > 50 V
Accuracy
± 0.1 % of set value ± 0.005 mA
Accuracy
-
-
1MRK505273-BEN D
r
r
55