VRF 50/60Hz
Step 6: Replace the faulty compressor and re- t the other compressors
•
Replace the faulty compressor.
•
If the oil had been spoiled and was drained from the non-faulty compressor
in Step 3, use clean oil to clean them before re-fitting it into the unit. To clean,
add oil into the compressor through the discharge pipe using a funnel, shake
the compressor, and then drain the oil. Repeat several times and then re-fit
the compressors into the units. (The discharge pipe is connected to the oil
pool of the compressor by the inner oil balance pipe.)
Step 7: Add compressor oil
Add oil to each of the compressors from which oil was drained in Step 3.
•
•
Only use RB75EA oil. Different compressors require different types of oil.
Using the wrong type of oil leads to various problems.
•
Add oil to the accumulator from which oil was drained in Step 4.
Step 8: Vacuum drying and refrigerant charging
•
Once all the compressors and other components have been fully connected, vacuum dry the system and recharge
refrigerant.
84
Figure 6-2.6: Compressor piping
Discharge pipe
Suction pipe