Figure 2-1.3: 48/56 model piping diagram
Key components:
1. Oil separator:
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separa on
efficiency is up to 99%.
2. Gas-liquid separator:
Stores liquid refrigerant and oil to protect compressor from liquid hammering.
3. Electronic expansion valve (EXV):
Controls refrigerant flow and reduces refrigerant pressure.
4. Four-way valve(ST1):
Controls refrigerant flow direc on. Closed in cooling mode and open in hea ng mode. When closed, the heat exchanger
func ons as a condenser; when open, the heat exchanger func ons as an evaporator.
5. High and low pressure switches:
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or
low pressure switches turn off, stopping the compressor. A er 5 minutes, the compressor restarts.