1 General Control Scheme Flowchart

Sec ons 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is ac vated.
Stop opera on
Abnormal shutdown
System stop
Standby control
Crankcase heater control
Startup control
Compressor startup delay control
Startup control for cooling opera on
Startup control for hea ng opera on
Normal opera on control
Component control during normal opera on
Compressor output control
Compressor step control
Electronic expansion valve control
Protec on control
High pressure protec on control
Low pressure protec on control
Discharge temperature protec on control
Compressor protec on control
Disable hea ng control
Thermo on
2
3
4
Special control
5
Condi ons met
for oil return
Condi ons met
for defros ng
6
Oil return opera on
Defros ng opera on
Legend
Numbers in the top right-hand
corners of boxes indicate the
relevant sec
n of text on the
following pages.
7
19