2.17 P2: Suction pipe low pressure protection (For all models)
2.17.1 Digital display output
P2
2.17.2 Description
•
Suction pipe low pressure protection.
•
The system stops running.
•
Error code is displayed on outdoor unit PCB.
2.17.3 Trigger / recover condition
•
Trigger condition: Suction pressure ≤ 0.05MPa.
•
Recover condition: Suction pressure ≥ 0.15MPa.
•
Reset method: Resume automatically.
2.17.4 Possible causes
•
Insufficient refrigerant.
•
Low pressure side blockage.
Poor evaporator heat exchange.
•
Main PCB damaged.
•
69