2.17 P2: Suction pipe low pressure protection (For all models)
2.17.1 Digital display output
P2
2.17.2 Description
Suction pipe low pressure protection.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.17.3 Trigger / recover condition
Trigger condition: Suction pressure ≤ 0.05MPa.
Recover condition: Suction pressure ≥ 0.15MPa.
Reset method: Resume automatically.
2.17.4 Possible causes
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.