2.16 P1: Discharge pipe high pressure protection (for 36-56 model)
2.16.1 Digital display output
P1
2.16.2 Description
•
Discharge pipe high pressure protection.
•
The system stops running.
•
Error code is displayed on the outdoor unit PCB.
2.16.3 Trigger / recover condition
•
Trigger condition: Discharge pressure ≥ 4.4MPa.
•
Recover condition: Discharge pressure ≤ 3.2MPa.
•
Reset method: Resume automatically.
2.16.4 Possible causes
Pressure sensor/switch not connected properly or has malfunctioned.
•
Excess refrigerant.
•
System contains air or nitrogen.
•
•
High pressure side blockage.
•
Poor condenser heat exchange.
•
Main PCB damaged.
67