2.3 E2: Communica on error between indoor and outdoor unit (For all models)
2.3.1 Digital display output
E2
2.3.2 Descrip on
Communica on error between indoor and outdoor unit.
The system stops running.
Error code is displayed on the outdoor unit PCB.
2.3.3 Trigger / recover condi on
Trigger condi on: Indoor units and the outdoor unit cannot communicate for 2 minutes a er the system is powered on
for 20 minutes.
Recover condi on: Communica on go back to normal.
Reset method: Resume automa cally.
2.3.4 Possible causes
Communica on wires between indoor and outdoor units not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagne c radia on.
Communica on wire too long.
Damaged main PCB or electric control box communica on terminals block.
Communica on wire break or poor contact for reasons (such as rat beat, or bond and connection).