BGH BV-V28W/DHN1 Service Manual page 62

Hide thumbs Also See for BV-V28W/DHN1:

Advertisement

VRF 50/60Hz
2.12 EP: Outdoor ambient temperature is lower than -5ºC in cooling operation (For all models)
2.12.1 Digital display output
EP
2.12.2 Description
Outdoor ambient temperature is lower than -5ºC in cooling opera on.
The system stops running.
Error code is displayed on outdoor unit PCB.
2.12.3 Trigger / recover condition
Trigger condi on: Outdoor ambient temperature is lower than -5ºC in cooling opera on.
Recover condi on: Outdoor ambient temperature is over -5ºC.
Reset method: Resume automa cally.
2.12.4 Possible causes
TL temperature sensor damaged.
TL temperature sensor connect to the main control board is loose.
Main PCB damaged.
2.12.5 Procedure
T4 sensor detected temperature is lower
T4 temperature sensor has short-
Replace outdoor main control board
62
EP
than -5ºC
No
circuited or failed
No
Yes
Temperature over opera on range
Yes
Replace the T4 sensor