Network Troubleshooting - ICT Digital 2 Series Instruction Manual

Hide thumbs Also See for Digital 2 Series:
Table of Contents

Advertisement

5.12. Network Troubleshooting

I am unable to access the embedded Web server:
 Check that you are using the correct IP address to access the
Status screen on the Control Panel display (see the Control
Panel Menus section for instructions on how to access the
Network Status screen). The IP address for the power supply
may have changed if DHCP is enabled.
If the Network Status screen on the Control Panel display shows
Network Not Connected, check the network cable connections to
the power supply and the network.
Ensure that you are using the correct type of network cable. An
industry standard "crossover" cable should be used for
should be used for connecting to a network.
Ensure the network card settings on your computer are
appropriate for accessing the IP address of the power supply. To
access a power supply with the default IP address of
192.168.0.181, typical network settings for your computer are:
o
o
o
If the HTTP port of the power supply has been changed, you
must append the port number to the URL used to access the
panel. See the Administrator Password / IP Address Reset
section for instructions on how to reset the port number to the
default setting.
I am not receiving e-mails from the power supply:
On the Network Setup page, ensure that the SMTP Server field is
entered correctly. The SMTP Port should be set to 25 for most
servers.
42
IP Address: 192.168.0.100
Subnet Mask: 255.255.255.0
Gateway: 192.168.0.1
Innovative Circuit Technology Ltd.
Network
-

Advertisement

Table of Contents
loading

Table of Contents