The Auto-Restart button will disable the supply output for
the Restart Delay period (see below) when clicked. This
feature can be useful when equipment powered by the unit
must be remotely power cycled to reboot operation.
NOTE: Using the ON/OFF or Auto-Restart button on a unit
configured as a Parallel Master will cause all Parallel units in a set to
disable their output, but will have no effect if used on a unit
configured as a Parallel Slave.
Output Settings: Used to change the output voltage or current limit
of the supply. To save any changes to the output settings, click on
Save Settings at the bottom of the page.
Output Voltage: This field sets the DC output voltage of the
power supply within the allowable range.
Current Limit: This field sets the DC output current limit of
the power supply within the allowable range.
Auto-Restart Delay: Set delay time (5 to 240s) that output will
remain off when output is remotely disabled using the Auto-Restart
button. The unit will then automatically restart after the Restart Delay
period.

5.3. Battery Backup

Use this page to view the battery status and set all battery related
parameters on units with the optional Battery/LVD port (SBC suffix
units). Click the Save Settings button after making changes to this
page.
Output Voltage Control: automatically adjust the output voltage of
the power supply according to the battery temperature, when the
optional temperature probe (ICT-TMP) is installed.
Temperature Coefficient/cell: set the desired temperature
change in -mV/°C per cell, according to the battery
disables the compensation. (A typical lead-acid
compensation value is -4mV/°C/cell, which is -24mV/°C for a
12V battery)
28
Innovative Circuit Technology Ltd.
The default setting of 0mV