Emerson Rosemount 3051N Reference Manual page 39

Smart pressure transmitter for nuclear service
Hide thumbs Also See for Rosemount 3051N:
Table of Contents

Advertisement

Reference Manual
00809-0100-4808, Rev CA
June 2008
FIGURE 3-2. Coplanar Flange
Mounting Configurations with
Optional Bracket (Code B4) for
Panel Mounting
2.8 (72)
6.2
(156)
2.81
(71)
4.8
(120)
NOTE
For steam service, do not blow down impulse piping through the transmitter.
Flush the lines with the blocking valves closed and refill the lines with water
before resuming measurement.
NOTE
When the transmitter is mounted on its side, position the Coplanar process
flange to ensure proper venting or draining. Keep drain/vent connections on
the bottom for gas service and on the top for liquid service.
NOTE
The Rosemount 3051N transmitter incorporates two independent seals
between the process connection and the conduit connection.
4.3 (110)
7.1
(181)
2.13
(54.1)
2.81
(71)
3
1
/
-16 x 1
/
8
4
Bolts for
Mounting to
Transmitter
3.4
(85)
Note
Dimensions are nominal in inches (millimeters).
Rosemount 3051N
5
/
Bolts for Panel
16
Mounting (not supplied)
3-5