en | Installing
Notice!
Risk of damage to equipment
To prevent damage to the relays, note these specifications:
- The maximum switching current is 1.25 A.
- The maximum switching voltage is 30 VDC.
i
- Only OHM resistive load can be connected to the relay.
- Inductive loads have to be short circuited using recovery diodes. The diodes (1N4004) are
supplied with every AMC2.
- If you need higher voltage or current for special applications, or electric door holding
magnets, you have to use coupling relays (e.g. Wieland flare move) on the outputs.
- Note that the coupling relays must be selected according to the supply voltage (12 V, 24 V)
of the AMC2.
NO/NC
Figure 4.21: Recovery diode schematic
Notice!
i
When you use the recovery diode, make sure to use it in the reverse direction.
2022-11 | V04 |
1
2
C
4
1
Normally open / normally closed
3
Inductive load
3
2
4
Guide d'installation
Access Modular Controller 2
Common
Recovery diode
Bosch Security Systems B.V.