FlameSpec UV-IR-HD User Manual
Medium Sensitivity
Fuel
N-Heptane
Gasoline
Methane
LPG
Diesel
JP5
Kerosene
Methanol
Ethanol
Isopropanol
Polypropylene
Paper
Low Sensitivity
Fuel
N-Heptane
LPG
JP5
Methanol
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com
Size
Distance ft (m)
1 x 1 ft
1 x 1 ft
32" plume
32" plume
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
Size
Distance ft (m)
1 x 1 ft
32" plume
1 x 1 ft
1 x 1 ft
F130V0020.06
Average Response
98 (30)
98 (30)
82 (25)
98 (30)
79 (24)
79 (24)
79 (24)
75 (23)
75 (23)
75 (23)
66 (20)
39 (12)
Average Response
49 (15)
49 (15)
39 (12)
39 (12)
Time (Seconds)
2.2
1.5
0.8
1.4
3.9
1.9
2.5
1.2
1.6
1.0
2.6
0.8
Time (Seconds)
1.2
1.4
8.8
1.2
37
Need help?
Do you have a question about the FlameSpec UV-IR-HD and is the answer not in the manual?