16 PARAMETER TABLE
Param.
Description
0
Desired water temperature
1
Difference to start heating cycle
2
Temp. to start electric heater
3*
Time delay to start electric heater
(min)
4
Desired
antilegionella program
5
Antilegionela time duration
6
Minimal time between two defrost
cycles
7
Evaporator temp. to start defrost
cycle
8
Evaporator temp. to stop defrost
cycle
9
Max. defrost time
10
Interval
antilegionella cycles
11
12
A
Water temperature above
B
Water temperature below
C
Evaporator temperature
D
Evaporation temperature
E
Gas temperature on compressor
outlet
F
EEV position
* On some unit models, set parameter need to be multiplied with factor 5.
Advice:
It is a fact that heat pump will work more efficient if the set water temperature will be set to lower water
temperature. We recommend that under the parameter »0«, the desired water temperature is set to 45°C, and
the antilegionella program cycle is set to minimal cycle 1 month.
Maximal water outlet temperature
Air temp.
Compressor
El. heater
water
temp.
during
between
two
T<-3°C
-
60°C
Range
Factory setting
10 - 70°C
2 - 15°C
10 - 90°C
0 – 90 min
60 - 90°C
0 - 90
30 - 90 min
-20 - 30°C
2 - 30°C
1 - 12 min
7 - 99 days
-9 – 99°C
-9 – 99°C
-9 – 99°C
-9 – 99°C
-9 – 99°C
-3°C<T<35°C
35°C<T
60°C
60°C
19
Note
48
Settable
5
Settable
50
Settable
45
Settable
60
Settable
0
Settable
45
Settable
-7
13
8
99
10
-
60°C