Troubleshooting - Trane 5 Series Service Facts

Convertible air handlers 1-1/2 to 5 ton, black epoxy/standard coil
Hide thumbs Also See for 5 Series:

Advertisement

CONSTANT TORQUE MOTOR TROUBLESHOOTING FOR GAM5
NOTE: The fan control has a 90
second "OFF" delay that is
factory set on. To turn this
feature off, turn dip switch to 0
and cycle power to the unit.
Turn off power.
Check set screw
position and motor
bearings. Correct
or replace as
needed.
Check operation
High voltage should
always be present.
Correct high voltage
wiring.
Correct wiring.
Check operation
NO
Is 24VAC measured
from terminal 8(G) to
NO
terminal 9(BL) on the
fan control?
YES
Replace fan control.
Check operation
About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications.
For more information, please visit www.trane.com or www.americanstandardair.com
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are
committed to using environmentally conscious print practices.
GAM5-SF-1P-EN 15 April 2020
Supersedes GAM5-SF-1N-EN (September 2018)
Turn comfort to
"FAN ON" mode
Motor does not run
Does blower
NO
wheel turn
freely?
YES
Is ~230 VAC measured
between terminals "L" &
NO
"N" on the motor?
See Figure 1
YES
Is ~24 VAC measured
between the wire connected
to "C" on the motor and the
wire connected to terminal 1
thru 5 on the motor?
See Figure 2
YES
Replace motor.
Check operation
Constant Torque Motor

Troubleshooting

FIGURE 1
FIGURE 2
This terminal block is located on
the motor. Look for labels below
on the motor side of the
connection.
© 2020