7.2.8 16(0x10) Set Multiple Registers (Write AO values)

This function code is used to set multiple holding registers that are used to store the configuration
valuesfor the iNS-308.
[Request]
Byte
Description
00
Net ID (Station Number)
01
Function Code
Starting
02-03
AO Address
Number of Registers
04-05
(Channels)
Byte count
06
Register Values
07
[Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
Starting
02-03
DO Address
Number of Registers
04-05
(Channels)
[Error Response]
Byte
Description
00
Net ID (Station Number)
01
Function Code
02
Exception Code
Copyright © 2022 ICP DAS CO., Ltd. All Rights Reserved.
Size
1 Byte
1 to 247
1 Byte
0x10
Byte 02 = high byte
2 Byte
Byte 03 = Low byte
Byte 04 = high byte
2 Byte
Byte 05 = Low byte
1 Byte n = (Points +7)/8
n= 1; Byte 03 = high byte
n= 2; Byte 04 = Low byte
n Byte
.......
n= m; Byte m+1 = high byte
Byte m+2 = Low byte
Size
1 Byte
1 to 247
1 Byte
0x10
2 Byte
The value is the same as Bytes 02-05 of the
Request
2 Byte
Size
1 Byte
1 to 247
1 Byte
0x90
Refer to the Modbus Standard
1 Byte
Specifications for more details
Value
Value
Value
- 43 -