ELECTRICAL CONNECTION

PLEASE NOTE: Electrical connection should only be completed by licenced personnel and in accordance with all
relevant New Zealand and Australian Standards, applicable laws and local legislations.
1. Remove the external cover to the electrical terminal by removing the screws and the terminal coverpanel.
2. Feed the electrical cable in through the conduit nipple and attach the electric supply wires to the applicable
Active Neutral and Earth connections located in the electrical terminal.
3. To complete the electrical connection, install electrical conduit, UF cable or other suitable means as specified (as
permitted by local electrical authorities) and connect the cable to a dedicated power supply branch circuit
equipped with the appropriate size circuit breaker, or time delay fuse protection.
INITIAL START UP AND COMMISSIONING
PLEASE NOTE: The water pump must be running and water circulating through the heat pump for the system to
operate.
1. Turn on your water filter pump and check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the Oasis unit.
3. Press the ON/OFF
4. To select the operating mode, press the "M" button to cycle to the sun icon (heating)
5. To set the temperature, press
6. Press
to increase the temperature, or press
7. Once the desired temperature is displayed, allow the screen to time out to set
8. After the system has been running for approximately 5 minutes; check the 2 temperatures displayed on the
screen and review the Temperature Differential (TD). The main temperature displayed is the cold water inlet
temperature, the small temperature display is the heated water outlet.
9. Adjust the water flow by opening or closing the 3-way valve installed at the cold-water inlet to achieve a target
TD of approximately 2°C (e.g. 22°C inlet water and 24°C outlet water)
10. If there is any interruption to water flow (i.e. when the water pump is turned off), the unit will automatically turn
off and display an E03 error code - no water flow. This is normal and the system will restart once water flow is
reinstated.
INITIAL HEAT UP TIME
Initial heat up times will vary depending on the size of your pool, environmental conditions and the capacity of the
system installed. After installation please allow the unit and pool pump to run continuously until the desired pool
water temperature is reached (it may take several days for the pool to initially reach the set temperature).
10
button of the controller for half a second, the heat pump will start within 60seconds
in the main interface, the current target-temperature will flash
to decrease the temperature