Compressor Applications - Siemens RDG20 KN Series Basic Documentation

Room thermostats with knx communications
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

Functions
4
Control sequences
Control output

4.7.10 Compressor applications

Application for compressor in
DX-type equipment
1-stage compressor
1-stage compressor with
reversing valve
1-stage compressor and electric
heater
(cooling only: disable electric
heater via P027)
1-stage compressor
for heating and cooling
2-stage compressor
Note
96 | 180
To limit the medium mix (heating and cooling medium), the changeover and the
control signal (DC 0...10 V) both work in sequence.
When control sequences change, the thermostat closes the combi valve and
releases the corresponding relay to operate the ball valve.
A delay of 120 seconds is needed before the combi valves can be operated by
the thermostat.
When the relay to ensure the ball valve is in the right H/C position, the control
signal for the combi valve is released.
If the thermostat is set with control sequence "H/C ceiling with PICV and 6-port ball
valve for changeover":
For PICV control, only output Y10 can be used to control the combi valve.
For 6-port ball valve as changeover :
Relay Q1 is energized, if "Heating sequence active" (P400 = 5, fixed,
cannot be changed)
Relay Q2 is energized, if "Cooling sequence active" (P401 = 6, fixed,
cannot be changed)
The wiring diagram of the application H/C ceiling with PICV and 6-port ball valve
for changeover is available in Connection diagrams [➙ 156].
For compressor applications,
Set the corresponding basic application as per Application overview [➙ 42].
Disable the fan (P350) or set the type of fan speed (P351)
Select the type of control outputs (On/Off, P201, P203, P204, P205)
The following applications are available:
Basic application Section
2-pipe
2-pipe
2-pipe with electric
heater
4-pipe
2-stage heating or
cooling
Minimum On/Off time:
Fan operation:
Fan speed:
Control outputs On/Off:
Control outputs DC 0...10 V:
2-pipe fan coil unit
[➙ 78]
2-pipe fan coil unit
[➙ 78]
2-pipe fan coil unit
with electric heater
[➙ 79]
4-pipe fan coil unit
[➙ 88]
2-stage heating
and cooling [➙ 83]
P212/P213 (only with On/Off control outputs)
P350 (0 = disabled, 1 = enabled)
P351 (1 = 1-speed, 2 = 3-speed,
3 = DC 0...10 V)
P201 = 4 (V1)
P203 = 4 (V2) (DC 0...10 V fan
only)
P201 = 5 (V1)
P203 = 5 (V2)
Sequences
H
( \ )
C
( / )
H + C
( \ / )
El. H + H
( ↯\ \ )
El. H + C
( ↯\ /)
C
( / )
H + C
( \ / )
H + H
( \ / )
C + C
( / / )
A6V11545892_en--_c