Object No. and name
1 System time
2 Date
3 Time of day
6 Fault transmission (0 = Disable / 1 = Enable)
94 Room operating mode: Status (receive)
7 Room operating mode: Preselection (receive)
9 Room operating mode: Preselection Auto
10 Room operating mode: Preselection Comfort
11 Room operating mode: Preselection Economy
12 Room operating mode: Preselection Protection
13 Room operating mode: Time switch
14 Room operating mode: Time switch Comfort
15 Room operating mode: Time switch Economy
16 Room operating mode: Time switch Protection
21 Room temp: [P19] Economy heating setpoint
22 Room temp: [P20] Economy cooling setpoint
23 Room operating mode: Window contact (0 = Close / 1 = Open)
24 Room operating mode: Presence detector (0 = NotOccupied /
1 = Occupied)
25 Room temp: Comfort basic setpoint
26 Room temp: Comfort setpoint abs (receive)
29 Setpoint heat set (receive)
30 Setpoint cool set (receive)
33 Room temperature: Comfort setpoint rel (receive)
36 External room temperature value
46 Heating/Cooling mode status (1 = Heating / 0 = Cooling) (receive)
48 Application mode
49 Dew point alarm (0 = No alarm / 1 = Alarm)
50 Enable fan command value (0 = Disable / 1 = Enable)
52 Fan command value
54 Fan speed 1 (0 = Off / 1 = On)
55 Fan speed 2 (0 = Off / 1 = On)
56 Fan speed 3 (0 = Off / 1 = On)
60 Outside temperature
76 Enable electric heater (0 = Disable / 1 = Enable)
78 External room relative humidity value [% r.h.]
79 Room rel. humidity: Setpoint high
80 Room rel. humidity: Setpoint low
81 Reset the Energy efficiency status (Green leaf)
(0 = No action / 1 = Reset)
83 Enable or disable Leaf indication (0 = Disable / 1 = Enable)
84 Keypad: Lock fan speed
85 Keypad: Lock fan speed in "auto" mode
86 Keypad: Lock the setpoint shift
87 Keypad: Lock the operating mode
92 Room temp: Current heating setpoint (receive)
93 Room temp: Current cooling setpoint (receive)
96 ChangeOverWater status (1=Heating/0=Cooling) (receive)
98 DC fan speed: [P359] Maximum speed heating
99 DC fan speed: [P360] Maximum speed cooling
101 External room air quality value
Input communication object
Output communication object
A6V11545892_en--_c
Thermostat
Object No. and name
RDG
4 Fault information
5 Fault status (0 = No alarm / 1 = Alarm)
8 Room operating mode: Preselection
17 Room operating mode: Status
18 Room operating mode: Comfort status
19 Room operating mode: Economy status
20 Room operating mode: Protection status
27 Room temp: Comfort setpoint abs (send)
28 Room temp: Current setpoint
31 Setpoint heat set (send)
32 Setpoint cool set (send)
34 Room temperature: Comfort setpoint rel (send)
35 Extended comfort mode status
37 Built-in room temperature value
38 Frost alarm (0 = No alarm / 1 = Alarm)
39 Heat alarm (0 = No alarm / 1 = Alarm)
40 X1: Temperature [° C]
41 X1: Digital (0 = Off /1 = On)
42 X2: Temperature [° C]
43 X2: Digital (0 = Off /1 = On)
44 U1: Temperature [° C]
45 U1: Digital (0 = Off /1 = On)
47 Heating/Cooling mode status (1 = Heating / 0 = Cooling) (send)
51 Fan operation (0 = Auto / 1 = Manual)
53 Fan output
57 Fan speed 1 (0 = Off / 1 = On)
58 Fan speed 2 (0 = Off / 1 = On)
59 Fan speed 3 (0 = Off / 1 = On)
61 Heating, control value continuous
62 Heating, control value continuous, seq 2
63 Cooling, control value continuous
64 Cooling, control value continuous, seq 2
65 Heating, control value status (0 = Inactive / 1 = Active)
66 Heating, control value status seq 2 (0 = Inactive / 1 = Active)
67 Cooling, control value status (0 = Inactive / 1 = Active)
68 Cooling, control value status seq 2 (0 = Inactive / 1 = Active)
69 Heating and cooling, control value status
(0 = Inactive / 1 = Active)
70 Heating and cooling, control value status seq2
(0 = Inactive / 1 = Active)
71 Heating and cooling, control value continuous
72 Heating and cooling, control value continuous seq 2
73 Control dehumidification (0 = Inactive / 1 = Active)
74 Control humidification (0 = Inactive / 1 = Active)
75 Hum. Control mode (inactive/hum/dehum)
77 Built-in room relative humidity value [%r.h.]
82 Energy efficiency status / Green Leaf (0 = Green / 1 = Red)
89 Room operating mode: Window contact (0=Close/1=Open)
88 Room operating mode: Presence detector
(0=NotOccupied/1=Occupied)
91 Room temp: Current heating setpoint (send)
90 Room temp: Current cooling setpoint (send)
95 ChangeOverWater status (1=Heating/0=Cooling) (send)
97 Manual fan command value (send)
100 Built-in room air quality value
102 DC damper demand
103 On/Off damper demand
Functions
Communication objects