Available op. mode End user
P002
Schedule via bus
1
3
2
Local schedule (P005 = ON)
1
2
3
N/A
Without time schedule
1
2
3
Window contact
Room operating mode:
Window contact
A6V11545892_en--_c
Description
op. mode
button
Recommended for commercial buildings:
Switching manually between modes by pressing the operating
mode button
User settings are temporary and valid until the next switching
event
Economy is not available
Note: Comfort mode can be temporarily extended (P102). (see
Different ways to influence operating mode [➙ 32])
Recommended for commercial buildings or rooms where manual
switching to Economy mode is desired:
Switching manually between modes by pressing the operating
mode button
User settings are temporary and valid until the next switching
event
Recommended for residential buildings or apartments:
Switching manually between modes by pressing the operating
mode button
Economy is available only with P002 = 2
User settings are permanent and valid until the next user
intervention or a new preselection mode from the bus
For residential buildings or apartments where the schedule is not
requested:
Switching manually between modes by pressing the operating
mode button
Economy is available only with P002 = 2
User settings are permanent and valid until the next user
intervention
Recommended for hotel guest rooms or apartments:
Switching manually between modes by pressing the operating
mode button
User settings are permanent and valid until the next user
intervention or a new preselection mode from the bus
The thermostat is forced into Protection mode when the window is open. The
contact can be connected to multifunctional input X1, X2 or U1. Set P150, P153 or
P155 to 3. User operations are ineffective and OFF displays if the window contact
is active.
The window contact function is also available via the KNX signal "Window contact",
e.g., from a KNX switch or a KNX presence detector.