Example 3:
Compressor and
reversing valve
164 | 180
Compressor application, with reversing valve (heating/cooling) and DC 0...10 V fan:
Commissioning
●
Application
●
Control output
●
Fan
●
Relay function
–
ON in demand: P401 = 2
–
Energized mode: Heating P401 = 5
–
Energized mode: Cooling P401 = 6
See Technical data [➙ 170] for min. and
max. ratings
4-pipe
P201 = 4 (On/Off)
P351 = 3
(or DIP6 = OFF)
Heating/cooling
Outputs used
●
M1
DC 0...10 V
fan
●
V1
*)
Reversing
valve
●
V2
*)
Compressor
●
K
Relay
*)
Release contact
RDG26..KN