Description Of Communication Objects - Siemens RDG20 KN Series Basic Documentation

Room thermostats with knx communications
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

Functions
4
Communication objects

4.13.2 Description of communication objects

Obj
Object name
1
System time
Time and date
System time for display on the room thermostat. See P009 (3 or 4)
2
Date
Date
Day, month and year for display on the room thermostat. See
P009 (3 or 4)
3
Time of day
Time of day
Another object for receiving the time of day for display on the room
thermostat. See P009 (3 or 4)
4
Fault information
Alarm Info
Common alarm output. If an alarm occurs, the alarm number is
transmitted.
5
Fault status
Alarm
Common alarm output. If an alarm occurs, the alarm flag is set.
6
Fault
Disable
transmission
Enable
A supervisory alarm system can disable the broadcasting of
alarms sent by the devices. This has no impact on the local
display of alarms. After a timeout of 48 hours, the sending of faults
is automatically enabled again.
7
Room operating
Auto
mode:
Comfort
Preselection
PreComf.
(receive)
Economy
Protection
Controls the room operating mode selection of the thermostat
(Manager) via bus.
The command can also be submitted as four 1-bit communication
objects (9...12). The last interaction wins – either from local
operating mode button or via bus.
Note: The thermostat will transform Pre-Comfort either into
Economy or Comfort (selectable via P910).
8
Room operating
Auto
mode:
Comfort
Preselection
Economy
(send)
Protection
Sends the room operating mode selection of the thermostat
(Manager) via bus.
The command can also be submitted as four 1-bit communication
objects (9...12). The last interaction wins – either from local
operating mode button or via bus.
128 | 180
Type/
Function
Flags
length
19.001
CWU
8 bytes
11.001
CWU
3 bytes
10.001
CWU
3 bytes
219.001
CRT
6 bytes
1.005
CRT
1 bit
1.003
CWU
1 bit
20.102
CWU
1 byte
20.102
CRT
1 byte
Obj
Object name
Room operating
Trigger
9
mode:
10
Preselection
11
- Auto
- Comfort
12
- Economy
- Protection
Switch room operating mode of manager to either Auto, Comfort,
Economy or Protection.
The last interaction wins – either from the local operating mode
button or via bus.
13
Room operating
Comfort
mode: Time
PreComf.
switch
Economy
Protection
This information is provided by a central schedule or a supervisor
and defines the actual HVAC operating mode of manager.
The command can also be submitted via three 1-bit
communication objects (14...16).
Protection has the highest priority and cannot be overridden.
Note: The thermostat transforms Pre-Comfort either into Economy
or Comfort (selectable via P910).
Room operating
Trigger
14
mode: Time
15
switch
16
- Comfort
- Economy
- Protection
Switch the HVAC mode to either Comfort, Economy or Protection
mode of manager.
17
Room operating
Comfort
mode: Status
Economy
Protection
Actual room operating mode used by the thermostat (Manager)
(considering time switch, user selection, window contact, etc.) This
state information is available via one 8-bit enumeration or three 1-
bit communication objects (18...20).
Room operating
ON
18
mode:
OFF
19
- Comfort status
20
- Economy status
- Protection
status
Corresponding communication object of manager sends "True".
Type/
Function
Flags
length
1.017
CW
1 bit
20.102
CWU
1 byte
1.017
CW
1 bit
20.102
CRT
1 byte
1.011
CRT
1 bit
A6V11545892_en--_c