Adding a Rack

Configuring
Suction Info
RS.8D.M2.22
Generate input for each
Shutdown phase loss
When all of the items on the Rack Info screen have been configured, press MENU to
return to the Main Menu.
There is only one way to add a rack. From the Main Menu select Configuration,
then Refrigeration, and the Rack Configuration screen appears. At the bottom left of
the screen are the words >> Add Rack<<. Move the cursor there and press
ENTER. A new Rack Info screen will appear.
Notice that the Rack Label field contains the letter B by default, since the previously
configured rack was rack A. You can change the default label if you want.
To configure a suction group, press MENU to return to the Main Menu, then select
Configuration, then Refrigeration. The Rack Configuration screen appears as at
left above. Select the rack and a Configure Rack menu appears (as at left below) .
AK2-SC 255 Reference Manual
digital input from a phase loss monitor.
[appears only after a Yes answer to the preceding
question] (List box) Whether there is a phase loss
input for each rack or each suction group.
[appears only after a Yes answer to the Monitor phase
loss question] (List box: Yes, No)